York AY012MA321 Air Conditioner User Manual


 
246814-YTG-D-0606
Unitary Products Group 13
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
AY024MA321
INDOOR COIL MODEL NO.
G2FD030S17
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
600 800 1000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 21.4 24.0 23.7 25.8 28.6 23.5 24.7 24.2 26.2 28.6 25.5 25.3 24.8 26.5 28.7
S.C. 20.6 19.1 16.1 16.3 13.0 22.7 21.8 18.6 18.3 14.3 24.7 24.5 21.0 20.4 15.6
KW 1.6 1.6 1.6 1.6 1.5 1.6 1.5 1.6 1.5 1.5 1.5 1.5 1.6 1.5 1.5
75
T.C. 20.9 23.0 22.6 25.0 27.5 22.6 23.6 23.2 25.2 27.5 24.4 24.2 23.8 25.4 27.4
S.C. 20.1 18.6 15.6 15.9 12.7 21.9 21.0 18.0 17.9 13.9 23.6 23.4 20.4 20.0 15.2
KW 1.8 1.7 1.8 1.7 1.7 1.7 1.7 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.7
85
T.C. 20.3 21.9 21.6 24.2 26.4 21.8 22.5 22.2 24.3 26.3 23.2 23.0 22.7 24.4 26.2
S.C. 19.7 18.1 15.1 15.4 12.4 21.1 20.2 17.5 17.5 13.6 22.5 22.3 19.8 19.6 14.8
KW 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
95
T.C. 19.7 20.9 20.6 23.4 25.4 20.9 21.4 21.1 23.4 25.2 22.1 21.9 21.7 23.4 25.0
S.C. 19.2 17.6 14.6 15.0 12.1 20.3 19.4 16.9 17.1 13.2 21.4 21.2 19.2 19.2 14.3
KW 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
105
T.C. 18.9 19.8 19.4 22.1 24.1 19.8 20.3 19.9 22.1 23.9 20.8 20.8 20.4 22.0 23.6
S.C. 18.3 17.0 14.1 14.5 11.6 19.2 18.6 16.3 16.6 12.8 20.2 20.1 18.5 18.7 13.9
KW 2.3 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
115
T.C. 18.0 18.8 18.3 20.9 22.9 18.8 19.2 18.7 20.8 22.6 19.6 19.7 19.1 20.8 22.3
S.C. 17.5 16.5 13.6 14.1 11.2 18.2 17.8 15.7 16.1 12.3 18.9 19.1 17.8 18.2 13.5
KW 2.5 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6
125
T.C. 17.1 17.7 17.3 19.6 21.7 17.7 18.2 17.5 19.5 21.3 18.3 18.6 17.8 19.5 21.0
S.C. 16.6 16.0 13.0 13.6 10.8 17.2 17.0 15.0 15.6 11.9 17.7 18.1 17.0 17.7 13.1
KW 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.9 2.8 2.8 2.8 2.8 2.9
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
MV12B FC/MC24B 1.03 1.04 0.94
MV12B FC/MC30B 1.03 1.04 0.94
MV12B FC/MC36B 1.03 1.04 0.94
MV12B G4FD030H17T2A 1.03 1.04 0.94
MV12B G4FD036H17T2A 1.03 1.04 0.94
MV16C FC/MC36C 1.03 1.04 0.94
AHP24 1.00 1.00 1.00
F4FP030H06T2A 1.00 1.00 1.00
FC/MC/PC24 1.00 1.00 1.00
FC/MC/PC30 1.00 1.00 1.00
FC/MC/PC36 1.00 1.00 1.00
G4FA036S17T2A 1.00 1.00 1.00
G4FA036S21T2A 1.00 1.00 1.00
G4FD030H17T2A 1.00 1.00 1.00
G4FD035H14T2A 1.00 1.00 1.00
G4FD036H17T2A 1.00 1.00 1.00
HC30 1.00 1.00 1.00
UC24 1.00 1.00 1.00
UC30 1.00 1.00 1.00
UC36 1.00 1.00 1.00
Variable Speed
Furnace
Coil T.C. S.C. KW
PV8*A12 FC/MC/PC24A 1.02 1.02 0.97
PV9*A12 FC/MC/PC24A 1.02 1.02 0.97
PV8*B16 FC/MC/PC24B 1.02 1.02 0.97
PV9*B12 FC/MC/PC24B 1.02 1.02 0.97
PV8*A12 FC/MC/PC30A 1.02 1.02 0.97
PV9*A12 FC/MC/PC30A 1.02 1.02 0.97
PV8*B16 FC/MC/PC30B 1.02 1.02 0.97
PV9*B12 FC/MC/PC30B 1.02 1.02 0.97
PV8*A12 FC/MC/PC36A 1.02 1.02 0.97
PV8*B16 FC/MC/PC36B 1.02 1.02 0.97
PV9*A12 FC/MC/PC36A 1.02 1.02 0.97
PV9*B12 FC/MC/PC36B 1.02 1.02 0.97
PV8*B16 G4FA036S17T2A 1.01 1.01 0.96
PV9*B12 G4FA036S17T2A 1.02 1.02 0.97
PV8*B16 G4FD030H17T2A 1.01 1.01 0.96
PV9*B12 G4FD030H17T2A 1.01 1.01 0.96
PV8*A12 G4FD035H14T2A 1.01 1.01 0.96
PV9*A12 G4FD035H14T2A 1.01 1.01 0.96
PV8*B16 G4FD036H17T2A 1.02 1.02 0.97
PV9*B12 G4FD036H17T2A 1.02 1.02 0.97
PV8*A12 HC30 1.02 1.02 0.97
PV9*A12 HC30 1.02 1.02 0.97