15. Commissioning Cont.
15.4 Adjustment of the gas pressure:
•
Remove the front
panel of the case.
• Open the gas valve
inlet pressure test
point (16 in Fig. 15.5)
at the valve input,
connect a suitable
pressure gauge and
check the gas
pressure of the supply
network.
• Remove the gauge
and close the
pressure test point
16.
• Open the gas valve
outlet pressure test
point (15 in Fig. 15.5)
and connect the
gauge.
E
15
16
F
G
Figure 15.5
• Remove the
protection cap I (Fig.
15.6) from the
mechanical pressure
adjustment
components levering
with a flat screwdriver
in the slots H.
• Start the boiler at its
maximum power.
H
I
Figure 15.6
• Ensure that the boiler
is not range rated.
• Rotate the maximum
gas pressure
adjustment (F in Fig.
15.5) until you obtain
the required pressure
(by rotating clockwise
the pressure
increases).
• Turn the boiler off
and disconnect one of
the two connectors (E
in Fig. 15.5).
• Start the boiler and
rotate the minimum
gas pressure
adjustment (G in Fig.
15.5) until you obtain
the required pressure
(by rotating clockwise
the pressure
increases).
• Turn the boiler off and
re-connect the wire to
the modulating
operator.
• Start the boiler and
check again the
maximum gas
pressure setting.
• Turn the boiler off and
disconnect the gauge.
Important: after the
checks all of the test
points must be sealed.
15.5 Checking the ignition device:
With the burner on high flame close the gas cock. After three ignition attempts (within
about three minutes), the lock-out signal lamp must appear (D on Figure 15.3). To reset
the boiler turn the knob B (figure 15.3) on the 0 position and then press and release the
boiler reset button (C on Figure 15.3).
RIVA HEAT ONLY MANUAL – REV A
32