Trane TWA075A-TWA200B Heat Pump User Manual


 
31SSP-PRC002-EN
Electrical
Data
Table ED-1— Electrical Characteristics — Motors — Air Handler
Standard Fan Motor Oversized Fan Motor
Unit Amps Amps
Model No. Volts Phase FLA LRA Phase FLA LRA
TWE050 380/415 3 1.4 8.2 3 1.8 21.6
TWE075 380/415 3 3.2 19.7 3 4.0 25.5
TWE100 380/415 3 3.6 25.5 3 5.3 37.5
TWE155 380/415 3 4.6 37.5 3 6.9 39.2
TWE200 380/415 3 7.6 39.2 3 9.0 65.1
Table ED-2 — Unit Wiring — Air Handler
Minimum Maximum Fuse
Unit Unit Operating Circuit Size or Maximum
Model No. Voltage Range Ampacity Circuit Breaker
TWE050 380/415 2 15
TWE075 380/415 4 15
TWE100 380/415 5 15
TWE155 380/415 6 15
TWE200 380/415 10 15
Table ED-4 — Unit Wiring — Heat Pumps
Minimum Maximum Fuse
Unit Unit Operating Circuit Size or Maximum
Model No. Voltage Range Ampacity Circuit Breaker
TWA075 380/415 12.6 50
TWA100 380/415 21.3 35
TWA155 380/415 28.4 35
TWA200 380/415 38.9 50
Table ED-3— Electrical Characteristics — Motors — 50 Cycle — Heat Pumps
Compressor Motor Condenser Fan Motor
Amps Amps
Unit RLA LRA FLA LRA
Model No. No. Volts Phase (Ea.) (Ea.) No. Volts Phase (Ea.) (Ea.)
TWA075AD 1 380/415 3 8. 8 90.0 1 380/415 1 1.6 3.7
TWA100AD 1 380/415 3 14.9 118.0 1 380/415 1 2.7 7.0
TWA155BD 2 380/415 3 11. 2 94.8 2 380/415 1 1.6 3.7
TWA200BD 2 380/415 3 14.9 118.0 2 380/415 1 2.7 7.0