29
Performance
Data
SSP-PRC002-EN
Table PD-23— Discharge Plenum And Grille Assembly Throw Distance — Air Handler
Unit Louver Angle Deflection Position
Model No. CFM m
3
/h Straight 20, ft (m) 40, ft (m) 55, ft (m)
1400 2378 38 (11.6) 24 (7.3) 22 (6.7) 18 (5.5)
1600 2718 42 (12.8) 31 (9.4) 26 (7.9) 20 (6.1)
TWE050 1800 3058 46 (14.0) 37 (11.3) 29 (8.8) 22 (6.7)
2000 3398 48 (14.6) 43 (13.1) 33 (10.1) 24 (7.3)
2200 3737 51 (15.5) 50 (15.2) 36 (11.0) 25 (7.6)
2100 3568 49 (14.9) 38 (11.6) 31 (9.4) 27 (8.2)
2400 4077 52 (15.9) 43 (13.1) 35 (10.7) 29 (8.8)
2700 4587 55 (16.8) 48 (14.6) 38 (11.6) 31 (9.4)
TWE075 3000 5097 58 (17.7) 53 (16.2) 42 (12.8) 32 (9.8)
3200 5436 56 (17.1) 46 (14.0) 38 (11.6) 30 (9.1)
3600 6116 62 (18.9) 51 (15.5) 42 (12.8) 33 (10.1)
4000 6795 66 (20.1) 57 (17.4) 47 (14.3) 35 (10.7)
4400 7475 71 (21.6) 62 (18.9) 52 (15.9) 38 (11.6)
TWE100 4800 8154 76 (23.2) 67 (20.4) 56 (17.1) 42 (12.8)
4300 7305 42 (12.8) 32 (9.8) 29 (8.8) 21 (6.4)
4900 8324 47 (14.3) 38 (11.6) 32 (9.8) 25 (7.6)
5400 9174 52 (15.9) 44 (13.4) 37 (11.3) 29 (8.8)
TWE155 5600 9514 50 (15.2) 40 (12.2) 33 (10.1) 27 (8.2)
6000 10193 57 (17.4) 49 (14.9) 41 (12.5) 32 (9.8)
6400 10873 56 (17.1) 46 (14.0) 38 (11.6) 30 (9.1)
7200 12232 62 (18.9) 51 (15.5) 42 (12.8) 33 (10.1)
TWE200 8000 13591 66 (20.1) 57 (17.4) 47 (14.3) 35 (10.7)
Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by
throw factor:
Terminal Velocity Throw Factor
50 fpm (.25 m/s) x 1.50
100 fpm (.51 m/s) x .75
150 fpm (.76 m/s) x .50
PD-24 — Static Pressure Drop Through Accessories — Air Handler
Discharge
Unit Return Grille Plenum and Grille
2
Electric Heaters (kW)
Model No. CFM m
3
/h In. wc
1
Pascal In. wc
1
Pascal 3.5-7 10-14 17-24 35
1400 2378 .09 (22.4) .16 (39.8) .06 .06 .12 —
TWE050A 1600 2718 .12 (29.9) .21 (52.3) 08 .08 .14 —
2000 3398 .18 (44.8) .33 (82.2) .13 .13 .19 —
2100 3568 .05 (12.5) .19 (47.3) .02 .03 .05 .08
TWE075A 2400 4077 .08 (19.9) .27 (67.2) .03 .06 .08 .12
3000 5097 .13 (32.4) .40 (99.6) .06 .12 .17 .23
TWE100A 2800 4757 .04 (10.0) .34 (84.7) .03 .04 .14 .20
TWE100B 3200 5436 .07 (17.4) .43 (107.1) .06 .13 .19 .26
4300 7305 .07 (17.4) .18 (44.8) .02 .02 .04 .05
4800 8154 .09 (22.4) .23 (57.3) .03 .03 .06 .08
TWE155B 5600 9514 .07 (17.4) .32 (79.7) .04 .04 .10 .15
6000 10193 .15 (37.4) .34 (84.7) .06 .06 .12 .17
TWE200B 6400 10873 .11 (27.4) .43 (107.1) .06 .0-6 .13 .19
8000 13591 .17 (42.3) .66 (164.3) .10 .10 .20 .30
1. Return air filter ESP included in Fan Performance Table data.
2. At louver opening angle of 42°F (5.5°C). For ESP at other angle openings, see accessory Installer’s Guide.
Throw distance values are based on a terminal velocity of 75 fpm (0.38 m/s).
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by
throw factor:
Terminal Velocity Throw Factor
50 fpm (.25 m/s) x 1.50
100 fpm (.51 m/s) x .75
150 fpm (.76 m/s) x .50
.