13
Performance
Data
SSP-PRC002-EN
(System)
Table PD-2 — Gross Cooling Capacities (MBh) TWA100A Heat Pump with TWE100A Air Handler (I-P)
Ambient Temperature (°F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (°F)
Bulb 61 67 73 61 67 73 61 67 73 61 67 73
CFM (°F) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
3000 75 101.6 80.9 111.8 67.1 122.7 45.2 97.7 79.0 107.6 65.4 118.1 43.6 93.6 76.9 103.2 63.6 113.2 41.9 89.4 74.8 98.6 61.7 108.2 40.1
80 102.1 94.6 112.0 77.2 122.7 59.2 98.4 92.6 107.8 75.3 118.0 57.5 94.4 90.6 103.4 73.5 113.2 55.7 90.4 88.6 98.8 71.5 108.2 53.8
85 104.6 104.6 112.1 90.6 122.8 72.8 101.3 101.3 107.9 88.7 118.2 71.1 97.9 97.9 103.5 86.7 113.4 69.3 94.3 94.3 98.9 84.6 108.4 67.4
90 109.6 109.6 112.7 104.1 122.9 86.4 106.3 106.3 108.6 102.2 118.3 84.6 102.8 102.8 104.4 100.2 113.5 82.8 99.1 99.1 100.1 98.2 108.5 80.7
3325 75 103.4 84.5 113.7 65.6 124.6 46.0 99.4 82.5 109.4 63.8 119.8 44.4 95.2 80.5 104.8 61.9 114.8 42.7 90.9 78.3 100.1 59.9 109.6 40.8
80 104.3 99.5 113.9 80.6 124.6 61.1 100.4 97.5 109.5 78.7 119.8 59.3 96.4 95.5 104.8 76.6 114.9 57.5 92.0 92.0 100.2 74.6 109.7 55.6
85 107.8 107.8 114.0 95.0 124.7 75.9 104.4 104.4 109.6 93.1 120.0 74.1 100.8 100.8 105.2 91.1 115.0 72.3 97.0 97.0 100.6 89.0 109.9 70.4
90 113.0 113.0 114.9 109.8 124.8 90.6 109.5 109.5 110.8 107.9 120.0 88.6 105.8 105.8 106.5 105.9 115.1 86.7 102.0 102.0 101.9 101.9 110.0 84.7
3650 75 105.0 88.0 115.3 67.7 126.1 46.8 100.9 85.9 110.8 65.8 121.2 45.0 96.6 83.9 106.1 63.9 116.1 43.2 92.2 81.7 101.3 62.0 110.8 41.3
80 106.2 104.2 115.4 83.8 126.1 62.8 102.3 102.3 110.9 81.7 121.3 61.1 98.0 98.0 106.2 79.7 116.2 59.2 94.3 94.3 101.4 77.6 111.0 57.4
85 110.6 110.6 115.6 99.3 126.3 78.8 107.0 107.0 111.2 97.3 121.4 77.0 103.3 103.3 106.7 95.3 116.4 75.2 99.4 99.4 102.0 93.3 111.1 73.3
90 115.9 115.9 117.0 115.4 126.3 94.4 112.3 112.3 112.2 112.2 121.5 92.5 108.4 108.4 108.4 108.4 116.5 90.5 104.5 104.5 104.4 104.4 111.3 88.5
3975 75 106.3 91.3 116.6 69.7 127.5 47.4 102.2 89.3 112.0 67.8 122.4 45.6 97.9 87.2 107.3 65.9 117.2 43.7 93.4 85.0 102.4 63.9 111.8 41.9
80 107.4 107.4 116.7 86.6 127.5 64.5 103.9 103.9 112.1 84.7 122.5 62.7 100.1 100.1 107.4 82.6 117.3 60.9 96.2 96.2 102.5 80.5 112.0 59.0
85 113.0 113.0 117.1 103.4 127.6 81.6 109.3 109.3 112.7 101.5 122.7 79.8 105.5 105.5 108.1 99.4 117.5 78.0 101.5 101.5 103.3 97.4 112.2 76.1
90 118.5 118.5 118.4 118.4 127.7 98.2 114.8 114.8 114.7 114.7 122.8 96.3 110.8 110.8 110.7 110.7 117.6 94.3 106.6 106.6 106.6 106.6 112.4 92.3
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.
Table PD-2 — Gross Cooling Capacities (kW) TWA100A Heat Pump with TWE100A Air Handler (SI)
Ambient Temperature (°C)
29.4 35.0 40.6 46.1
Enter.
Dry Entering Wet Bulb (°C)
Bulb 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8 16.1 19.4 22.8
m
3
/h (°C) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.
5098 24 29.7 23.7 32.7 19.7 35.9 13.2 28.6 23.1 31.5 19.1 34.6 12.8 27.4 22.5 30.2 18.6 33.1 12.3 26.2 21.9 28.9 18.1 31.7 11.8
27 29.9 27.7 32.8 22.6 35.9 17.3 28.8 27.1 31.6 22.1 34.6 16.8 27.6 26.5 30.3 21.5 33.2 16.3 26.5 25.9 28.9 20.9 31.7 15.8
29 30.6 30.6 32.8 26.5 35.9 21.3 29.7 29.7 31.6 26.0 34.6 20.8 28.7 28.7 30.3 25.4 33.2 20.3 27.6 27.6 29.0 24.8 31.7 19.7
32 32.1 32.1 33.0 30.5 36.0 25.3 31.1 31.1 31.8 29.9 34.6 24.8 30.1 30.1 30.6 29.3 33.2 24.2 29.0 29.0 29.3 28.8 31.8 23.6
5648 24 30.3 24.7 33.3 19.2 36.5 13.5 29.1 24.2 32.0 18.7 35.1 13.0 27.9 23.6 30.7 18.1 33.6 12.5 26.6 22.9 29.3 17.5 32.1 11.9
27 30.5 29.1 33.3 23.6 36.5 17.9 29.4 28.6 32.1 23.0 35.1 17.4 28.2 28.0 30.7 22.4 33.6 16.8 26.9 26.9 29.3 21.8 32.1 16.3
29 31.6 31.6 33.4 27.8 36.5 22.2 30.6 30.6 32.1 27.2 35.1 21.7 29.5 29.5 30.8 26.7 33.7 21.2 28.4 28.4 29.4 26.1 32.2 20.6
32 33.1 33.1 33.6 32.2 36.5 26.5 32.1 32.1 32.4 31.6 35.1 25.9 31.0 31.0 31.2 31.0 33.7 25.4 29.9 29.9 29.8 29.8 32.2 24.8
6203 24 30.7 25.8 33.8 19.8 36.9 13.7 29.5 25.2 32.4 19.3 35.5 13.2 28.3 24.6 31.1 18.7 34.0 12.7 27.0 23.9 29.7 18.1 32.5 12.1
27 31.1 30.5 33.8 24.5 36.9 18.4 30.0 29.9 32.5 23.9 35.5 17.9 28.7 28.7 31.1 23.3 34.0 17.3 27.6 27.6 29.7 22.7 32.5 16.8
29 32.4 32.4 33.8 29.1 37.0 23.1 31.3 31.3 32.6 28.5 35.6 22.6 30.2 30.2 31.2 27.9 34.1 22.0 29.1 29.1 29.9 27.3 32.5 21.5
32 33.9 33.9 34.3 33.8 37.0 27.6 32.9 32.9 32.8 32.8 35.6 27.1 31.8 31.8 31.7 31.7 34.1 26.5 30.6 30.6 30.6 30.6 32.6 25.9
6754 24 31.1 26.7 34.1 20.4 37.3 13.9 29.9 26.1 32.8 19.9 35.9 13.3 28.7 25.5 31.4 19.3 34.3 12.8 27.3 24.9 30.0 18.7 32.7 12.3
27 31.5 31.5 34.2 25.4 37.3 18.9 30.4 30.4 32.8 24.8 35.9 18.4 29.3 29.3 31.4 24.2 34.4 17.8 28.2 28.2 30.0 23.6 32.8 17.3
29 33.1 33.1 34.3 30.3 37.4 23.9 32.0 32.0 33.0 29.7 35.9 23.4 30.9 30.9 31.6 29.1 34.4 22.8 29.7 29.7 30.3 28.5 32.9 22.3
32 34.7 34.7 34.7 34.7 37.4 28.8 33.6 33.6 33.6 33.6 35.9 28.2 32.4 32.4 32.4 32.4 34.4 27.6 31.2 31.2 31.2 31.2 32.9 27.0
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.