Chilled-Water System Design
notes
Primary-Secondary (Decoupled) Configuration
If the water flow through the chillers (production) could be hydraulically
isolated from the water flow through the coils (distribution), many of the
problems encountered in parallel and series configurations could be
eliminated.
Figure 47 shows a configuration that separates, or decouples, the production
capacity from the distribution load. This scheme is known as a primary-
secondary system, also referred to as a decoupled system. This
configuration is unique because it dedicates separate pumps to the
production and distribution loops. A bypass pipe that connects the supply
and return pipes is the key component in decoupling the system.
The chillers in the production loop receive a constant flow of water, while the
coils in the distribution loop, controlled by two-way modulating valves, receive
a variable flow of water.
Primary-Secondary Configuration