Trane TRG-TRC016-EN Air Conditioner User Manual


 
96 TRG-TRC016-EN
notes
period four
Chiller-Plant Control
System Optimization
The chiller-plant control system can also be used for system optimization.
For the purposes of this discussion, we will define optimization as minimizing
the energy used by the chiller plant (including chillers, chilled-water pumps,
condenser-water pumps, and cooling tower) while still maintaining comfort
or satisfying process loads.
The first step is to examine the energy use of the major components of the
chiller plant, to see what can be done to minimize each component individually.
The chiller energy usage can be reduced by lowering the condenser-water
temperature or by raising the chilled-water temperature.
In a variable-flow system, chilled-water pumping energy can be reduced by
lowering the chilled-water temperature while increasing the system T. With
the lower water temperature and increased T, the coil requires less water
flow to handle the same load.
Cooling-tower energy can be reduced by increasing the condenser-water
temperature. This allows the tower fans to cycle or slow down. Condenser-
water pumping energy can be reduced by increasing the T through the
condenser side of the system, thereby pumping less water. This is achieved
by reducing the water flow through the condenser.
Obviously, looking at only a single component presents a conflicting picture for
energy reduction, and a change in one component has an impact on other
components. To truly optimize the chiller plant, all components must be
analyzed together.
System Optimization
Chiller
Decrease condenser-water temperature
Increase chilled-water temperature
Chilled-water pump (variable-flow system)
Increase chilled-water T
Cooling tower
Increase condenser-water temperature
Condenser-water pump (variable-flow system)
Increase condenser-water T
Figure 104