Basic Unit Characteristics Outdoor Fan Motor
Model
Number
Electrical
Characteristics
Allowable
Voltage
Range
Minimum
Circuit
Ampacity
Maximum
Fuse
Size
Qty. HP
Amps
FLA
Amps
LRA
CTA090A1 208-230/60/1 187-254 15 15 1 1/2 3.1 8.1
CTA090A2 460/60/1 414-506 15 15 1 1/2 1.6 3.7
CTA090A8 575/60/1 518-632 15 15 1 1/2 1.2 3.0
CTA120A1 208-230/60/1 187-254 15 15 1 1 6.0 17.0
CTA120A2 460/60/1 414-506 15 15 1 1 2.7 7. 0
CTA120A8 575/60/1 518-632 15 15 1 1 2.0 5.7
CTA120B1 208-230/60/1 187-254 15 15 1 1 6.0 17.0
CTA120B2 460/60/1 414-506 15 15 1 1 2.7 7. 0
CTA120B8 575/60/1 518-632 15 15 1 1 2.0 5.7
CTA180B1 208-230/60/1 187-254 15 15 2 1/2 3.1 8.1
CTA180B2 460/60/1 414-506 15 15 2 1/2 1.6 3.7
CTA180B8 575/60/1 518-632 15 15 2 1/2 1.2 3.0
8 PKG-SVX17A-EN
Table 1: CTA Unit Electrical Data
Electrical