Trane PKGP-PRC001-EN Heat Pump User Manual


 
28
PKGP-PRC001-EN
Electrical
Data
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection, Continued)
Standard Indoor Motor Oversize Indoor Motor
To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or
Tons With Model No. KW Rating
1
Stages MCA Max Circuit Breaker
2
MCA Max Circuit Breaker
2
208/230 Volts Three Phase
AYDHTRK318A 13.5/18.0 1 113/120 125/125 119/127 125/150
WCD150B3 AYDHTRK336A 27.0/36.0 2 160/175 175/175 166/181 175/200
AYDHTRK354A 40.5/54.0 2 207/229 225/250 213/235 225/250
12½
AYHHTRN318A 13.5/18.0 1 113/120 125/125 119/127 125/150
WCH150B3 AYHHTRP336A 27.0/36.0 2 160/175 175/175 166/181 175/200
AYHHTRP354A 40.5/54.0 2 207/229 225/250 213/235 225/250
AYDHTRK318A 13.5/18.0 1 124/131 125/150 130/137 150/150
WCD180B3 AYDHTRK336A 27.0/36.0 2 171/185 175/200 177/191 200/200
AYDHTRK354A 40.5/54.0 2 218/240 225/250 224/246 225/250
15
AYHHTRN318A 13.5/18.0 1 124/131 125/150 130/137 150/150
WCH180B3 AYHHTRP336A 27.0/36.0 2 171/185 175/200 177/191 200/200
AYHHTRP354A 40.5/54.0 2 218/240 225/250 224/246 225/250
AYDHTRL336A 27.0/36.0 2 190/204 200/225 197/212 200/225
WCD240B3 AYDHTRL354A 40.5/54.0 2 237/258 250/300 244/266 250/300
AYDHTRK372A 54.0/72.0 2 284/312 300/350 291/320 300/350
20
AYHHTRN336A 27.0/36.0 2 190/204 200/225 197/212 200/225
WCH240B3 AYHHTRN354A 40.5/54.0 2 237/258 250/300 177/266 250/300
AYHHTRN372A 54.0/72.0 2 284/312 300/350 224/320 300/350
NOTES:
1. Heater kw ratings are at 208/240 for 208/230V unit
480V for 460 V unit
2. HACR type circuit breaker per NEC.
*Indicates both downflow and horizontal units.