Trane PKGP-PRC001-EN Heat Pump User Manual


 
14
PKGP-PRC001-EN
Performance
Data
(15 Ton)
*Indicates both downflow and horizontal units.
Table PD-3 — Gross Cooling Capacities (MBh) 15 Ton Downflow and Horizontal Three Phase WC*180B
Ambient Temperature ( F)
85 95 105 115
Enter.
CFM Dry Entering Wet Bulb (F)
Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 170.0 133.0 186.0104.0 194.0 71.6156.0 126.0180.0 100.0 194.0 69.4 141.0 118.0 166.0102.0 189.0 66.1125.0110.0 150.0 95.1177.0 60.6
5400 80 170.0 157.0 186.0 126.0 196.0 96.2 157.0 150.0 180.0 123.0 195.0 93.4 143.0 142.0 167.0 117.0 189.0 89.3 130.0 130.0 150.0 109.0 177.0 83.8
85 175.0175.0 188.0 147.0 197.0 114.0 165.0 165.0 181.0 146.0 196.0 115.0 153.0 153.0 167.0 140.0 190.0 113.0 141.0 141.0 151.0 132.0 178.0 107.0
90 183.0 183.0189.0169.0199.0133.0177.0 177.0182.0169.0197.0136.0165.0165.0169.0164.0190.0135.0153.0153.0153.0153.0178.0130.0
75 173.0 140.0 187.0 115.0 195.0 71.9 160.0 133.0 183.0 105.0 195.0 70.8 145.0 125.0 170.0 109.0 191.0 67.7 129.0 117.0 153.0 101.0 181.0 62.1
6000 80 175.0 165.0 189.0 130.0 197.0 100.0 162.0 159.0 183.0 129.0 197.0 98.9 148.0 148.0 171.0 123.0 191.0 92.5 135.0 135.0154.0 115.0 181.0 87.3
85 180.0180.0 190.0 153.0 199.0 115.0 172.0 172.0184.0 153.0 198.0 118.0 160.0 160.0 171.0 148.0 192.0 117.0 148.0 148.0 155.0 140.0 181.0 112.0
90 188.0 188.0192.0175.0201.0136.0183.0183.0186.0178.0200.0140.0173.0173.0175.0174.0193.0141.0160.0160.0160.0160.0182.0137.0
75 176.0 145.0 189.0 119.0 196.0 74.1 164.0 140.0 185.0 107.0 196.0 72.2 148.0 132.0 174.0 115.0 193.0 68.6 132.0 123.0 157.0 108.0 183.0 64.8
6600 80 178.0172.0 191.0 133.0 198.0 99.0 166.0 166.0 186.0 134.0 197.0 98.4 153.0 153.0 175.0 129.0 193.0 95.5 140.0 140.0 157.0 121.0 184.0 90.6
85 184.0184.0 192.0 157.0 201.0 120.0 178.0178.0 187.0 160.0200.0 121.0 166.0 166.0 175.0 156.0 194.0 121.0 153.0 153.0 159.0 149.0 184.0 118.0
90 191.0 191.0194.0181.0203.0140.0187.0 187.0189.0186.0202.0144.0179.0179.0179.0179.0196.0146.0167.0 167.0166.0166.0185.0144.0
75 179.0 151.0 190.0 122.0 197.0 75.3 167.0 146.0 187.0 111.0 197.0 73.5 151.0 138.0 177.0 121.0 194.0 69.1 135.0 130.0 159.0 114.0 185.0 65.5
7200 80 181.0 179.0 192.0 136.0 199.0 100.0 171.0 171.0 188.0 138.0 199.0 99.9 158.0 158.0 177.0 135.0 195.0 98.4 145.0 145.0160.0 127.0 186.0 93.4
85 187.0 187.0 194.0 161.0 202.0 122.0 182.0182.0 189.0 166.0 201.0 124.0 172.0 172.0179.0 164.0 196.0 125.0 159.0159.0 162.0 156.0 186.0 123.0
90 194.0 194.0196.0186.0205.0144.0191.0 191.0 191.0 191.0203.0148.0184.0184.0184.0184.0198.0151.0172.0172.0172.0172.0187.0150.0
NOTES:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity