Apply 1.25-inch x 0.33-inch
ribbed butyl tape to the shipping
split channel and shipping split
plates (see Figure 11).
Verify the section is level prior to
proceeding with the next section
of the unit.
Figure 11. Apply butyl tape to shipping splits
Move the next unit section as
close as possible from the
previous section. The two
sections should be close enough
to reduce the amount of
dragging required. This is
particularly important when
mounting on a roof curb to
minimize damage to the sealant
on the roof curb. Alignment of
sections must be completed
before drawing sections
together.
Remove the bottom bolts from
the shipping split lifting lugs (see
Figure 12).
Figure 12. Remove bottom bolts from
lifting lugs