Toshiba RAS-13YKV-E Air Conditioner User Manual


 
– 57 –
No. Part name
1 Electrolytic capacitor
(For raising pressure,
smoothing)
2 Converter module
Checking procedure
1. Turn OFF the power supply breaker.
2. Discharge all four capacitors completely.
3. Check that safety valve at the bottom of capacitor is not broken.
4. Check that vessel is not swollen or exploded.
5. Check that electrolytic liquid does not blow off.
6. Check that the normal charging characteristics are shown in
continuity test by the tester.
C12, C13, C14 500µF/400V
1. Turn OFF the power supply breaker.
2. Discharge all four capacitors completely.
3. Check that the normal rectification characteristics are shown in
continuity test by the tester.
MCC-808
Soldered
surface
Heat sink IGBT side
C12 C13 C14 C15
Case that product is good
Pointer swings once, and
returns slowly. When
performing test once again
under another polarity, the
pointer should return.
Resistance value
in good product
Diode check IGBT check
Tester rod
+ ~ ~ A
21
+ ~
1
~
2
A
Mark
E G
E G
+
~
1
~
2
+
~
1
~
2
E
~
1
~
2
Resistance value
in good product
50k
or more
(0 in trouble)
50k
or more
(0 in trouble)
Tester rod
+
~
2
~
1
~
2
G
E
A
10-8-5. Checking Method for Each Part