Toshiba RAS-13YKV-E Air Conditioner User Manual


 
20
6-2. Operation Data
<Cooling>
<Heating>
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5 m
Temperature
condition (°C)
Heat exchanger
pipe temp.
Indoor Outdoor
Model name
Standard
pressure
P (MPa)
T1 (°C) T2 (°C)
Indoor fan
mode
Outdoor fan
mode
Compressor
revolution
(rps)
10YKV-E 0,8 to 1,0 9 to 11 42 to 44 High High 56
27/19 35/
13YKV-E 0,8 to 1,0 8 to 10 46 to 48 High High 85
Temperature
condition (°C)
Heat exchanger
pipe temp.
Indoor Outdoor
Model name
Standard
pressure
P (MPa)
T1 (°C) T2 (°C)
Indoor fan
mode
Outdoor fan
mode
Compressor
revolution
(rps)
10YKV-E 3,5 to 3,7 42 to 44 2 to 4 High High 70
20/ 7/6
13YKV-E 2,5 to 2,7 50 to 52 0 to 3 High High 97