Toshiba RAS-09LAV-UL Air Conditioner User Manual


 
7-2. O
p
eration Data
<Coolin
g
>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P Psia (MPa) T1 °F (°C) T2 °F (°C) (rps)
80/67 98/75 137 to 160 54 to 57 99 to 102
(26.7/19.4) (35/23.9) (0.9 to 1.1) (12 to 14) (37 to 39)
116 to 145 52 to 55 104 to 107
(0.8 to 1.0) (11 to 13) (42 to 44)
<Heating>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) RAS- pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P Psia (MPa) T1 °F (°C) T2 °F (°C) (rps)
70/60 47/43 363 to 392 102 to 105 32 to 37
(21.1/15.6) (8.3/6.1) (2.5 to 2.7) (39 to 41) (0 to 3)
377 to 406 106 to 106 32 to 36
(2.6 to 2.8) (41 to 43) (0 to 2)
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 16 ft (5m)
62
High High 64
09LKV-UL
12LKV-UL
High High
12LKV-UL High High 77
High High 6009LKV-UL
FILE NO. SVM-10019
23