– 22 –
RAS-12LKV-UL / RAS-12LAV-UL
NOTE :
• The maximum pipe length of this air conditioner is 66ft (15 m). When the pipe length exceeds 50ft (15m), the additional
Max. : 66ft (20m)
Deoxidized copper pipe
Outer dia. : 3/8 in. (9.52mm)
Thickness : 1/32 in. (0.8mm)
NOTE :
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
INDOOR UNIT
T1
TO
Temp. measurement
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 1/4 in. (6.35mm)
Thickness : 1/32 in. (0.8mm)
Sectional shape
of heat insulator
Allowable height
difference : 33ft (10m)
Allowable pipe length
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse Modulating
valve at liquid side
Ø1.2 x 80
Ø1.2 x 80
TD
4-way valve
Compressor
DA111A1F-20F1
TS
T2
Outdoor heat
exchanger
Split capillary
Temp. measurement
Propeller fan
Refrigerant amount : 2.43 lbs (1.10kg)
OUTDOOR UNIT
Muffler
Muffler
TE
TC
TA
charging of refrigerant, 0.22 oz/ft (20g/m) for the part of pipe exceeded 15m is required. [Max. 0.22 lbs (100g)]
Min. : 6.6ft (2m)
Chargeless : 50 ft (15m)
Charge : 0.22oz/ft
(51 to 66 ft)
[20g/m (16 to 20m)]
FILE NO. SVM-10019