Toshiba R410A Air Conditioner User Manual


 
9
Waterproof rubber cap
Base plate
Drain nipple
Knockout hole
Waterproof rubber cap
Open
Drain nipple
<SM560AT-E>
<SM800AT-E>
When there is a possibility of freezing of drain at the
cold district or a snowfall area, be careful for drainage
ability of drain. The drainage ability increases when a
knockout hole on the base plate is opened. (Open the
knockout hole to outside using a screwdriver, etc.)
Optional Installation Parts
(Local Procure)
Refrigerant Piping Connection
CAUTION
TAKE NOTICE THESE IMPORTANT
4 POINTS BELOW FOR PIPING WORK
1. Keep dust and moisture away from inside the
connecting pipes.
2. Tightly connect the connection between pipes
and the unit.
3. Evacuate the air in the connecting pipes using
VACUUM PUMP.
4. Check gas leak at connected points.
<Piping connection>
A
B
C
Parts name
Refrigerant piping
Liquid side : Ø6.35 mm or Ø9.52 mm
Gas side : Ø12.7 mm or Ø15.9 mm
Pipe insulating material
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
Q’ty
Each one
1
Each one
Capacity
rank
RAV-
SM560
SM800
Liquid side
Outer
Thickness
diameter
Ø6.4 0.8
Ø9.5 0.8
Gas side
Outer
Thickness
diameter
Ø12.7 0.8
Ø15.9 1.0
For Reference
If a heating operation would be continuously performed
for a long time under the condition that the outdoor
temperature is 0°C or lower, draining of defrosted water
may be difficult due to freezing of the bottom plate,
resulting in a trouble of the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally for a safety installation of the air conditioner.
For details, contact the dealer.