Toshiba R410A Air Conditioner User Manual


 
50
External view
REQUIREMENT
The hanging bolt pitch on horizontal direction (B) is not halved at center with the ceiling opening size.
Therefore, check the relational position in the following figure.
Dimension
RAV-SM561BT
RAV-SM801BT
RAV-SM1101, 1401BT
In case of concrete slab
A hole-in-anchor, a hole-in-plug, or a hole-in-bolt is used.
ABCDEFGHJKMN
700 766 690 750 780 12.7 6.4 252 280 280 1 2
1000 1066 990 1050 1080 15.9 9.5 252 580 290 2 3
1350 1416 1340 1400 1430 15.9 9.5 252 930 310 2 4
In case of steel structure
Angle is used as it is, or a support angle is newly set.
Hanger bolt
Hanging bolt
Support angle
110
129
44
49
Knock-out hole Ø125
(Air take-in port)
6-Ø4 Tapping screw undersized
hole Ø160
Hanging bolt pitch 700
5941
Main unit dimension 800
75
Hanging bolt pitch B
Main unit dimension A
J = M x K H
Discharge port flange
N-Ø200
Hanging bolt
4-M10 screw
(Arranged
locally)
60~260
9
Suction port
canvas
(Separate sold)
C
Ceiling open size D
Panel external dimension E
Panel C.L
410
Ceiling open size 470
Panel external dimension 500
Ø26 Power supply,
remote controller
cable take-out port
Refrigerant pipe
connecting port
(Liquid side ØG)
Suction port
flange
(Separate sold)
Suction port
panel
(Separate sold)
Drain pipe connecting port
for vinyl chloride pipe
(Inner dia. 32, VP. 25)
41
196
393
498
638
50
131
243
50
Refrigerant pipe
connecting port
(Gas side ØF)
174
320
3
INSTALLATION OF INDOOR UNIT