STT40 / STT70
Functional description 6-21
DEFAULT SETTINGS FOR JUMO TEMP. CONTROLLER
Model number: dTRON 16.1 B 70.3011
Contact information:
Germany USA
MoltkestraBe 13-31 885 Fox Chase, Suite 103
36035 Fulda, Germany Coatesville, PA 19320, USA
Ph: +49 661 60 03-7 27 Ph: 610-380-8002 or 1-800-554-JUMO
Fax: +49 661 60 03-5 08 Fax: 610-380-8009
E-mail: mail@jumo.net Email: info@JumoUSA.com
Internet: www.jumo.net Internet: www.JumoUSA.com
PARAMETERS THAT ARE CHANGED IN TESTING AREA
CELSIUS FAHRENHEIT
FACTORY DEF. ACS VALUE ACS VALUE DESCRIPTION
C112 2 0 0 0 C 2 0 0 0 = C 2 0 3 0 = F
NOTE: DEG. C TO DEG. F CONVERSION
SPL -200 40 Deg. C 104 Deg. F LOW TEMP LIMIT
SPH 850 140 Deg. C 284 Deg. F HIGH TEMP LIMIT (STANDARD)
SPH 850 180 Deg. C 356 Deg. F HIGH TEMP LIMIT (REQUIRES AFTER COOLER)
AL1 0 20 Deg. C 68 Deg. F HIGH TEMP ALARM BAND
rASd 0 5 19 RAMP GRADIENT
PARAMETERS THAT ARE NOT CHANGED (FACTORY DEFAULTS)
SCL 0 0 START VALUE RANGE FOR STD. SIGNALS
SCH 100 100 END VALUE RANGE FOR STD. SIGNALS
OFFS -200 -200 PROCESS VALUE CORRECTION (OFFSET)
AL2 0 0 LIMIT FOR LIMIT COMPARATOR 2
Pb1 0 7 PROPORTIONAL BAND 1(CONTROLLER OUT 1)
Pb2 0 0 PROPORTIONAL BAND 2(CONTROLLER OUT 2)
dt 80 s 9 s DERIVATIVE TIME
rt 350 s 36 s
Cy 1 20.0 s 7.4 s SWITCHING CYCLE TIME(CONTROLLER OUT 1)
Cy 2 20.0 s 20 s SWITCHING CYCLE TIME(CONTROLLER OUT 2)
db 0 0 CONTACT SPACING
HYS 1 1 1 SWITCHING DIFFERENTIAL1(CONTROLLER OUT 1)
HYS 2 1 1 SWITCHING DIFFERENTIAL2(CONTROLLER OUT 2)
y.0 0% 0% WORKING POINT
y.1 100% 100% OUTPUT LIMITATION: MAX OUTPUT
y.2 -100% -100% OUTPUT LIMITATION: MIN OUTPUT
Df 0.6 s 1.2 s FILTER TIME CONSTANT FOR ADAPTATION
raSD 0 9 RAMP GRADIENT
SP1 Process Temp Process Temp SET POINT FOR PROCESS TEMPERATURE
SP2 Process Temp Process Temp USED FOR SECOND HEATER
C111 0 0 0 0 0 0 0 0 PARAMETER SETTINGS
C113 0 5 3 4 0 5 3 4 PARAMETER SETTINGS
C114 1 0 0 1 1 0 0 1 PARAMETER SETTINGS
Note: 1) Please consult the JUMO dTRON temperature controller O&I manual for
further explanation of the above parameter settings.
2) Some factory default settings may change as the unit is run continuously.
RESET TIME