Sanyo R410A Air Conditioner User Manual


 
30
11-3. Tools Specifically for R410A
For servicing, use the following tools for R410A
To prevent other refrigerants (R22, R407C) from being mistakenly charged to this unit, sizes of the service ports and
flare nuts of the narrow tube service valve and wide tube service valve have been altered.
Tool Distinction Tool Name
Gauge manifold
Charging hose
Gas leak detector
Refrigerant cylinder
Charging cylinder
Refrigerant recovery unit
Vacuum pump with anti-reverse flow (*1)
(Solenoid valve-installed type, which prevents oil from flowing back into the unit when
the power is off, is recommended.)
Vacuum pump (*2) can be used if the following adapter is attached.
Vacuum pump adapter (reverse-flow prevention adapter) (*3).
(Solenoid valve-installed adapter attached to a conventional vacuum pump.)
Electronic scale for charging refrigerant
Flare tool
Bender
Torque wrench
Cutter, reamer
Welding machine, nitrogen gas cylinder
Tools specifically for R410A
Tools which can be com-
monly used for R22,
R407C, and R410A
CAUTION
The above tools specifically for R410A must not be used for R22 and R407C.
Doing so will cause malfunction of the unit.
For the above vacuum pump (
*
1,
*
2) and vacuum pump adapter (
*
3), those for
R22-type units can be used for R407C-type. However, they must be used exclu-
sively for R410A and never alternately with R22 and R407C.