9
3-7. Recommended Wire Length and Diameter
Regulations on wiring diameter differ from locality to
locality. For field wiring requirements, please refer to
your local electrical codes. Carefully observe these regu-
lations when carrying out the installation.
Table 5 lists recommended wire lengths and diameters
for power supply systems.
Refer to the wiring system diagram (Fig. 18) for the
meaning of “A” and “B” in Table 5.
Table 5
2
4
2
4
11
INDOOR
UNIT
Terminal
OUTDOOR
UNIT
(B)
Terminal
(A)
L2
L1
G
G
G
230V/208V
230V/208V
230V/208V
(Inter-unit)
power line
Grounding line
Grounding
line
Power supply
Single-phase 230V/208V 60HZ
Disconnect
switch
Field supply
Fig. 18
WARNING
●
Be sure to comply with local
codes on running the wire
from the indoor unit to the
outdoor unit (size of wire and
wiring method, etc.).
●
Each wire must be firmly
connected.
●
No wire should be allowed to
touch refrigerant tubing, the
compressor, or any moving
part.
CAUTION
Be sure to connect the power
supply line to the outdoor unit
as shown in the wiring dia-
gram. The indoor unit draws its
power from the outdoor unit.
To avoid the risk of electric
shock, each air conditioner
unit must be grounded.
WARNING
#
…
AWG (American Wire Gauge)
WIRING SYSTEM DIAGRAM
AWG
Model
C2462R,CL2462R 64 (Max.) 132 (Max.) 35A
(A) Power Supply
Wiring Length (ft.)
(B) Inter-Unit
Power Line
Fuse or Circuit
Capacity
(#12)
(#14)