INSTALLATION
SAFETY LABEL
This is a copy of the label that accompanies
each L900-NG and L900-LP Direct Vent Gas
Fireplace. We have printed a copy of the
contents here for your review. The safety label
is located on the right hand side of the unit,
visible when the exterior right side brick panel
is removed.
NOTE: Regency
®
units are constantly being
improved. Check the label on the unit and if
there is a difference, the label on the unit is
the correct one.
COPY OF SAFETY DECAL
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfi tter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, fl exible
connectors shall not exceed 36 inches in
length.
For the State of Massachusetts, the appli-
ances individual manual shut-off must be a
t-handle type valve.
The State of Massachusetts requires the
installation of a carbon monoxide alarm in
accordance with NFPA 720 and a CO alarm
with battery back up in the same room where
the gas appliance is installed.
Minimum Clearances to Combustibles from Fireplace
Non-Combustible Hearth Extension
Side Walls *A 16" (406mm)
Ceiling B 49" (1245mm)
Min. Mantel Height C 17-1/2" (445mm)
Max. Mantel Depth **D 13” (330mm)
Alcove Width E 84" (2134mm)
Alcove Depth F 36" (914mm)
VENTED GAS FIREPLACE HEATER
This appliance must be installed in accordance with the manufacturer’s installation
instructions and with local codes, if any; if none, follow the current ANSI Z223.1 in
the USAor the current CAN 1-B149 in Canada.
This vented gas fireplace heater is not for use with air filters.
For Manufactured Home Installation: This Direct Vent System Appliance must be
installed in accordance with the manufacturer's installation instructions and
ManufacturedHome Constructionand SafetyStandardTitle24 CFR,Part 3280,or the
currentStandardfor FireSafetyCriteria forManufacturedHomeInstallation, Sites,and
CommunitiesANSI/NFPA501A,andwithCAN/CSAZ240MHMobileHomeStandardin
Canada.
Thisappliance isonly foruse withthe typeof gasindicated onthe ratingplate andmay
be installed in an aftermarket, permanently located, manufactured (mobile) home
where not prohibited by local codes. See owner'smanual for details. This appliance is
notconvertibleforusewithothergases,unlessacertifiedkitisused(Kit#546-969).
CertifiedforusewithHeatWave(Kit#946-556)andHeatRelease(Kit#946-570).
Forusewithglassdoorscertifiedwiththeapplianceonly.
Electrical Supply: 115 V, 0.1 A, 60 Hz
NOT FOR USE WITH SOLID FUEL
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ETIQUETTE
Listed: VENTED GAS FIREPLACE HEATER
Tested to: ANSI Z21.88-2005/ CAN/CGA-2.17-M91,
Certified for / Certifiée pour: CANADA AND U.S.A.
CSA 2.33-2005,
ANSI Z21.50b-2003/ CSA 2.22b-2003
Serial No. / No de serie
320
`
NATURAL GAS FIREPLACE: MODEL L900-NG
Factory Equipped For Altitude 0-4500ft. (0-1372m)
Min. Supply Pressure 5“ WC (1.25 kpa)
Low Setting Man. Pressure 1.6" WC (0.39 kpa)
Max. Manifold Pressure 3.5" WC (0.87 kpa)
Orifice Size (Front Burner) #47 DMS
Orifice Size (Back Burner) #30 DMS
Minimum Input 11,000 Btu/h (3.22 )
Maximum Input 48,000 Btu/h (14.06 kW)
kW
D
E
F
H
G
A
B
C
Model/Modele:
L900-NG
Model/Modele:
L900-LP
918-609
PROPANE GAS FIREPLACE: MODEL L900-LP
Factory Equipped For Altitude 0-4500ft. (0-1372m)
Min. Supply Pressure 12" WC (2.98 kpa)
Low Setting Man. Pressure 3.6" WC (0.9 kpa)
Max. Manifold Pressure 10" WC (2.49 kpa)
Orifice Size (Front Burner) #56 DMS
Orifice Size (Back Burner) #50 DMS
Minimum Input 9,500 Btu/h (2.78 kW)
Maximum Input 46,500 Btu/h (13.62 kW)
Hearth Height G 2" (51mm)
Hearth Width H 33-1/8” (841mm)
FPI Fireplace Products International Ltd., Delta BC, CANADA
MADE IN CANADA / FABRIQUE AU CANADA
I
* Alcove side wall must have a min. of 16” (406mm) clearance on one side.
** Mantel depth taken at 27-1/2” (699mm) from front facing.