Regency 946-523/P Indoor Fireplace User Manual


 
Venting Arrangements - Horizontal
Terminations
This lightly shaded area of the diagram shows allowable combinations
of vertical runs with horizontal terminations, using one 45° and one
90° elbow (two 45º
elbows equal one 90° elbow).
Note: Must use optional rigid pipe adapter (Part # 510-994) when
using Rigid Pipe.
Maintain clearances to combustibles.
Horizontal vent must be supported every 3 feet.
Firestops are required at each oor level and whenever passing
through a wall.
A vent guard may be required as per local codes, refer to Exterior
Vent Termination Locations.
Note: FPI Direct Vent System (Flex) is only approved for horizontal
terminations.
P33 Gas Fireplace
* Unit must be raised by 1” when using
Contemporary Faceplate
Please refer to Exterior Vent Terminations for
additional guidelines on vent locations.
35August 2008 Product Speci cations Book
Gas Fireplaces
Gas Fireplaces