Regency 946-523/P Indoor Fireplace User Manual


 
Vertical Venting with Two (2) 90° Elbows
- Initial vertical section.
Two 45° elbows = One 90° elbow
Option V H V+ V1 Maximum total pipe: length, of
all sections, must not exceed
30 feet.
Total horizontal sections must
not exceed 8 feet.
Minimum of 1 foot between
90° elbows is required.
A) 1’ Min. 4’ Max. 2’ Min.
B) 2’ Min. 5’ Max. 3’ Min.
C) 3’ Min. 6’ Max. 4’ Min.
D) 4’ Min. 7’ Max. 5’ Min.
E) 5’ Min. 8’ Max. 6’ Min.
Vertical Venting with Two (2) 90° Elbows
- Initial horizontal section.
Two 45° elbows = One 90° elbow
Option H + H1 V Maximum total pipe: length, of
all sections, must not exceed
30 feet.
Total horizontal sections must
not exceed 6 feet.
Minimum of 1 foot between
90° elbows is required.
A) 2’ Max. 2’ Min.
B) 3’ Max. 3’ Min.
C) 4’ Max. 4’ Min.
D) 5’ Max. 5’ Min.
E) 6’ Max. 6’ Min.
Vertical Venting with Three (3) 90°
Elbows - Initial vertical section.
Two 45° elbows = One 90° elbow
Option V H + H1 V+ V1 Maximum total pipe: length, of
all sections, must not exceed
30 feet.
Total horizontal sections must
not exceed 8 feet.
Minimum of 1 foot between
90° elbows is required.
A) 2’ Min. 3’ Max. 4’ Min.
B) 3’ Min. 4’ Max. 6’ Min.
C) 4’ Min. 5’ Max. 7’ Min.
D) 5’ Min. 6’ Max. 8’ Min.
E) 6’ Min. 7’ Max. 9’ Min.
F) 7’ Min. 8’ Max. 10’ Min.
Vertical Venting with Three (3) 90°
Elbows - Initial horizontal section.
Two 45° elbows = One 90° elbow
Option H V H + H1 V+ V1 Maximum total pipe:
length, of all sections,
must not exceed 30
feet.
Total horizontal sections
must not exceed 7
feet.
Minimum of 1 foot
between 90° elbows
is required.
A) 1’ Max. 1’ Min. 3’ Max. 3’ Min.
B) 2’ Max. 2’ Min. 4’ Max. 5’ Min.
C) 3’ Max. 3’ Min. 5’ Max. 7’ Min.
D) 4’ Max. 4’ Min. 6’ Max. 9’ Min.
E) 5’ Max. 5’ Min. 7’ Max. 11’ Min.
P33 Gas Fireplace
34 August 2008 Product Speci cations Book
Gas Fireplaces
Gas Fireplaces