Regency 946-523/P Indoor Fireplace User Manual


 
P33 Gas Fireplace
Combustible Mantels with
Contemporary Faceplate
Because of the extreme heat this replace emits, the mantel
clearances are critical. Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed
anywhere in the shaded area or higher.
Mantel Leg Clearances with
Contemporary Faceplate
Combustible mantel leg clearances from side of unit as per diagram
below:
Clearances are from the nished edge of the unit or an installed front.
Caution Requirements
The top, back and sides of the replace are de ned by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this replace and vent
system be installed only in accordance with these instructions.
Clearance: Dimension Measured
From:
A: *Front Floor Clearance
(min.)
1" (25mm) Underside of
Unit
B: *Sidewall 7-1/2" (241mm) Side of Unit
C: *Ceiling
(room and/or alcove)
30" (889mm) Top of Unit
D: Alcove Width 48" (1219mm) Sidewall to
Sidewall
(Minimum)
E: Alcove Depth 36" (914mm)
Front to
Back Wall
(Maximum)
Flue Clearances to
Combustibles
Horizontal - Top 2-1/2"
Horiztonal - Side 1-1/2"
Horiztonal - Bottom 1-1/2"
Vertical (Flex Vent) 1-1/2"
Vertical (Rigid) 1-1/4"
*Note: All measurements are from the top/side
of the unit, not optional front.
Clearance Requirements with
Contemporary Faceplate
Top View
0-3
WARNING
Failure to maintain required clearances is a major cause of chimney related res.
Installation of this replace must comply with these clearances
Please note: Due to ongoing product development, product appearance and speci cations
are subject to change without notice.