Regency 946-523/P Indoor Fireplace User Manual


 
Framing and Finishing
1) Determine the total thickness of facing material (e.g. drywall plus
ceramic tiles) to allow the nished surface to be ush with the front
of the unit. Total facing thickness can vary from 1/2” (13mm) to 1-¼”
(32mm) thick.
2) Frame in the enclosure for the unit with framing material.
3) For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapor barrier and drywall, as per local
installation codes. (Do not insulate the replace itself.)
4) The top of the unit must not be closer than 30” (762mm) to the
ceiling.
5) Combustible material may be brought up to the top and
sides of the unit and be covered with ceramic tiles, bricks,
rock or other suitable combustible finishing materials.
Note: The unit does not have to be completely enclosed in a
chase. The clearance on top of the unit is 0” to the standoffs
so combustible building materials can be laid directly on top
of the standoffs. You must maintain proper clearances from
the vent to combustible materials (See Below).
6) Use metal studs for framing where the minimum clearance from
the vent to combustible material cannot be maintained.
P33 Gas Fireplace
Combustible Mantels
Because of the extreme heat this replace emits, the mantel
clearances are critical. Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed
anywhere in the shaded area or higher.
Drywall
Mantel Clearances
2
0
12
6
4
810
0
Side View
Top of
Unit
12"(305mm)
3-1/2"(89mm)
7-1/2"(191mm)
A
3” (76mm)
Standoff
B
C
D
Note: If desired a non-combustible mantel may be installed at a
lower height.
Note: Ensure the paint that is used on the mantel and the facing
is “heat resistant” or the paint may discolour.
Mantel Leg Clearances
Combustible mantel leg clearances as per diagram below:
Clearances are from the nished edge of the unit or an installed front.
Maximum
1-1/2” projection at 2”
minimum clearance.
Mantel Clearances
ABCD
Front 29” (737mm) 11” (279mm) 9” (229mm) 7” (178mm)
WARNING
Failure to maintain required clearances is a major cause of
chimney related res. Installation of this replace must comply
with these clearances.
Clearance: Dimension Measured From:
A: Mantel Height 7” (178mm) Minimum (Additional on this page)
B: Sidewall 7-1/2” (191mm) Side of installed front
C: Ceiling 30” (762mm) Top of installed unit
D: Mantel Depth 12” (305mm) Maximum (Additional on this page)
E: Alcove Width 48” (1219mm) Sidewall to Sidewall (Minimum)
F: Alcove Depth 36” (914mm) Front to back wall (Maximum)
Top of Hearth must not be higher than the base of the rebox.
Vent Clearances Clearance Dimension
Horizontal - Top 2-1/2” (64mm)
Horizontal - Side 1-1/2” (38mm)
Horizontal - Bottom 1-1/2” (38mm)
Vertical - Flex 1-1/2” (38mm)
Vertical - Rigid 1-1/4” (32mm)
E
B
B
A
C
D
F
Clearance Requirements
30 August 2008 Product Speci cations Book
Gas Fireplaces