Raypak 5042004 Boiler User Manual


 
43
C
heck Power Supply
W
ith multi-meter at incoming power, check voltage
between:
Hot - Common (≈120 VAC)
Hot - Ground (≈120 VAC)
Common - Ground (< 1 VAC)
Attach Manometers to Measure Pressures
1. Turn off main gas valve.
2. Attach (1) 12” scale manometer to an upstream
bleedle valve on the gas supply pipe to the heater
(Measure point “A” in Fig. 48).
3. Attach (1) 24” scale manometer to the manifold
pressure tap located on the elbow downstream of
the valve (Measure point “D” in Fig. 48).
4. Attach (1) 12” scale manometer near the fan-prov-
ing switch. Pull black cap from air pressure switch
tee and connect the manometer. NOTE: Retain
caps for reinstallation later.
Check Gas Supply Pressure
1. Slowly turn on main gas shut-off valve.
2. Read the gas supply pressure from the manome-
ter; minimum supply pressure for natural gas is 4.0
in. WC, recommended supply is 7.0 in. WC, mini-
mum supply pressure for propane gas is 4.0 in.
WC, recommended supply is 11.0 in. WC (dynam-
ic readings, full fire input).
WARNING: If Common - Ground is > 1 VAC,
STOP: Contact electrician to correct ground failure.
Failure to do this may burn out 120V-24V
transformer, or may cause other safety control
damage or failure.
Start-Up
1. Turn power on.
2. Turn on the heater, wait approximately 15 seconds
after the blower starts, and the igniter should start
to glow (observable through the observation port
located at the front, bottom of the heater). Look
into the sight glass located at the bottom of the
front panel to check igniter operation. Gas valve
should open in 45-60 seconds.
3. The heater ignites at 50% of full rate (as indicated
on the LCD display of the temperature control
located in the upper right of the front panel).
4. If the burner fails to light on the first trial, it will try
for ignition up to three times before going into lock-
out with the standard ignition module. If the heater
is equipped with the optional single-try ignition
module, it will go into lockout.
5. Wait until the controller indicates 100% on the fir-
ing rate display screen (approximately 30
seconds).
Blower Check
1. Check blower suction using the manometer
attached to the fan pressure switch tee, with the
heater firing at 100% input. The reading should be
as noted in Table V for both natural and propane
gas.
2. FOR REFERENCE ONLY: Measure the blower
amp draw with the heater firing at 100% input and
compare the measured value to the values in
Table U. The amp draw is measured with a clamp-
on type amp probe clamped to the 14 AWG black
power wire going into the blower.
3. When firing at 100%, the desired heater combus-
tion CO2 is between 8.5 and 9.0% for natural gas
and 9.5 and 10.0% for propane with CO less than
100 ppm. If this combustion cannot be achieved
GAS
TO BURNER
A
B
C
D
Fig. 48: Gas Pressure Measurement Locations
3. If the gas pressure is greater than 14.0 in. WC,
turn off the main gas shut-off valve, upstream of
the heater.
NOTE: The values in Tables V, W and X represent
the conditions when the heater is at full firing rate at
sea level.
NOTE: Pressure and combustion data are provided
with the heater.