A. Hearth Protection Requirements
FLOOR PROTECTION: Floor protector must be non-com-
bustible material, extending beneath heater and to the front,
sides and rear as indicated. The oor must be non-com-
bustible or otherwise adequately protected from radiant heat
given off by the unit and from sparks and falling embers. A
layer of thin brick or ceramic tile over a combustible fl oor is
not suffi cient.
For the Millennium Model In US installations, i
t is nec-
essary to install a fl oor protector of a minimum of 3/8 inch
(9.5mm) thick metal clad millboard or equivalent a minimum
of 16
inches (406mm) in front of glass and 8 inches (203mm)
to both sides of the fuel loading door. Open the door and
measure 8 inches (203mm) from the side edge of the open-
ing in the face of the appliance. *See exception.
16 in. from glass
8 in.
Fuel loading door
4-7/8 in.
3-1/8 in.
31-5/8 in.
minimum
39-5/8 in.
minimum
Must extend 2 in. (51mm) beyond
each side of pipe (shaded area)
203mm (8 in.)
203mm
(8 in.)
203mm
(8 in.)
457mm (18 in.)
1260mm
(49-5/8 in.)
minimum
1041mm (41 in.)
minimum
In Canada, similar oor protection must be provided 18
inches (457mm) in front and 8 inches (203mm) from the
sides and rear of the stove. *See exception.
*EXCEPTION: Non-combustible oor protections must
extend beneath the fl ue pipe when installed with horizontal
venting and extend 2 inches (51mm) beyond each side.
See Figure 12.4.
USA required
Canada recommended
Figure 12.3
4
Installation
Figure 12.1
Figure 12.2
Figure 12.4
WARNING
Fire Risk.
Hearth pads must be installed exactly as
specified.
High temperatures or hot embers may ignite
concealed combustibles.
Millennium Model
31-5/8 in.
27-3/8 in.
31-3/4 in.
38-15/16 in.
3-1/16 in.
135°
optional
coverage
51-1/16 in.
USAUSA
CANADA