Quadra-Fire 31M-ACC-MBK Stove User Manual


 
July 7, 2011
7033-277I
Page 11
3100 Wood Stove Series (ACC)
R
B. Clearances to Combustibles (UL and ULC)
BACKWALL / SIDEWALL
A
B
C
D
E
F
E
F
CORNER INSTALLATION
G
H
*
90° OFF TOP
UP & OUT CEILING
CLEARANCE
STOVE TO CEILING
CLEARANCE
C
D
ALCOVE TOP VIEW
G
A
B
ALCOVE SIDE VIEW
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having jurisdiction
Fire Risk.
Comply with all minimum clearances to
combustibles as specifi ed.
Failure to comply may cause house fi re.
WARNING
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS In Inches & (Millimeters)
NOTE: All "A" , "C" and "F" Dimensions are to the inside diameter of the flue collar.
A B C D E F G H
INSTALLATION: Full Vertical OR Horizontal with Minimum 2 FT Vertical Off Stove Top
SINGLE WALL PIPE
Flat Top Model 15.25 (387) 11.75 (298) 25.5 (648) 16 (406) 8 (203) 17 (432) 48 (1220) 12 (305)
Step-Top Model 12 (305) 8.5 (216) 22 (559) 12.5 (318) 5.5 (140 14.5 (368) 48 (1220) 12 (305)
DOUBLE WALL PIPE
Flat Top Model 10.5 (267) 6.5 (165) 22 (559) 13 (330) 6.5 (165) 15.5 (394) 48 (1220) 9 (229)
Step-Top Model 10 (228) 6 (152) 20.5 (521) 11 (279) 4 (102) 13 (330) 48 (1220) 9 (229)
INSTALLATION: 90° Elbow Off Top of Stove Through Backwall
SINGLE WALL PIPE
Flat Top Model 12 (305) 8.5 (216) 22 (559) 13 (330) 8 (203) 17 (432) 48 (1220) 12 (305)
Step-Top Model 10 (254) 6 (152) 20.5 (521) 11 (279) 5.5 (140) 14.5 (368) 48 (1220) 12 (305)
DOUBLE WALL PIPE
Flat Top Model 8 (203) 4.5 (114) 17.5 (445) 8.5 (216) 6.5 (165) 15.5 (394) 48 (1220) 9 (229)
Step-Top Model 10 (254) 6 (152) 20.5 (521) 11 (279) 4 (102) 13 (330) 48 (1220) 9 (229)
INSTALLATION: ALCOVE
Six inch (6") (152mm) diameter listed Double Wall air insulated connector pipe with UL103 HT* listed
factory-built Class "A" chimney, or a masonry chimney. (Mobile Home must be equipped with a spark arrestor). Maximum depth of Alcove
shall be no more than 48 inches (1220mm) with a minimum height of 48 inches (1220mm) to top of unit, and the referenced clearances.
*In Canada must comply with CAN/ULC-S269 M87 for the 650
o
C Factory-built chimney.
DOUBLE WALL PIPE
Flat Top Model 11.75 (298) 8.25 (210) 23.5 (597) 14.5 (368) N/A N/A 48 (1220) *
Step-Top Model 10 (254) 6.5 (152) 20.5 (521) 11 (279) N/A N/A 48 (1220) *
* SEE PIPE MANUFACTURERS CLEARANCES - NOT TESTED
NOTE: Service Space
In order to replace the tube channel assembly a clearance
of 19 inches (483mm) is required on the right side of stove
in order to remove the tubes with the stove in place.
If space is not available, the stove will have to be discon-
nected from the chimney to proceed with the tube replace-
ment.