43
GAS-FIRED HEATER Installation Manual
BE FACING UP
SIDEWALL VENT WITH
INTAKE
EXHAUST
IMPORTANT:
INTAKE LEG MUST
EXTERIOR WALL
CONCENTRIC VENT KIT
FRONT VIEW
SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING
MIN.
1"
Fig. 7-11 2” sidewall vent with 2” concentric vent
kit (KGAVT0501CVT)
12" MIN.
TOP VIEW
(TEE)
INTAKE
EXHAUST
(STRAIGHT
COUPLING)
1" MIN.
RIGHT SIDE VIEW
(TEE)
EXHAUST
INTAKE
EXTERIOR WALL
COUPLING)
(STRAIGHT
SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING
12" MIN.
1" MIN.
Fig. 7-9 2” sidewall vent with tee (intake) and
coupling (exhaust)
NOTE: EXTENDED VENT
RUNS WHEN TRANSITIONING
TO A LARGER DIAMETER
MUST ALWAYS TAKE PLACE
IN A VERTICAL POSITION
TO PREVENT CONDENSATE
BLOCKAGE.
EXTERIOR WALL
TOP VIEW
EXHAUST
VENT KIT
INTAKE
SIDEWALL VENTING WITH KIT
RIGHT SIDE VIEW
VENT KIT
EXHAUST
SUPPORT BRACKETS
MUST BE USED ON
ALL HORIZONTAL
AND VERTICAL PIPING
Fig. 7-10 2” sidewall vent with V500 kit
I. DIAGRAMS FOR SIDEWALL VENTING
**Important Note: All vent pipes must be
glued, properly supported, and the exhaust
must be pitched a minimum of a 1/4" per
foot back to the heater (to allow for
drainage of condensate).
NOTE: When placing support brackets on vent piping, the first bracket must be within 1 foot of the
appliance and the balance at 4 foot invervals on the vent pipe. The heater venting must be readily
accessible for visual inspection for the first three feet from the heater.