Mitsubishi P120 Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 253 -
HWE09120 GB
(2) Inverter output related troubles
Items to be checked Phenomena Remedy
[1]
Check the INV
board error
detection cir-
cuit.
<P72 model> 1) IPM/overcurrent breaker trip
Error code: 4250
Detail code: No. 101, 104, 105, 106,
and 107
Replace the INV board.
(1) Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
2) Logic error
Error code: 4220
Detail code: No. 111
Replace the INV board.
(2) Put the outdoor unit
into operation.
3) ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
Replace the INV board.
4) IPM open
Error code: 5301
Detail code: No.119
Normal
<P96, P120, P144
models>
1) IPM/overcurrent breaker trip
Error code: 4250
Detail code: No. 101, 103, 104, 105,
106, and 107
See the section "Troubleshooting
the IPM" ( Refer to - 6 - [5] ).
Replace the IPM, and put the out-
door unit back into operation.
If the problem persists, replace the
INV board.
(1) Disconnect the invert-
er output wire from
the output terminals
(U, V, W) of the IPM.
2) Logic error
Error code: 4220
Detail code: No. 111
See the section "Troubleshooting
the IPM" ( Refer to - 6 - [5] ).
Replace the IPM, and put the out-
door unit back into operation.
If the problem persists, replace the
INV board.
Replace the INV board, and put
the outdoor unit back into opera-
tion.
If the problem persists, replace the
DCCT.
(2) Put the outdoor unit
into operation.
3) ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
Replace the INV board.
4) DCCT sensor circuit failure
Error code: 5301
Detail code: No.118
Replace the DCCT board.
Replace the DCCT, and put the
outdoor unit back into operation.
If the problem persists, replace the
INV board.
5) IPM open
Error code: 5301
Detail code: No.119
Normal
[2]
Check for
compressor
ground fault or
coil error.
Disconnect the compres-
sor wiring, and check the
compressor Meg, and coil
resistance.
1) Compressor Meg failure
Error if less than 1 Mohm.
When no liquid refrigerant in the
compressor
Replace the compressor
Check that no liquid refrigerant in
the compressor.
2) Compressor coil resistance failure
Coil resistance value of 0.20 ohm
(20°C [68°F]) : P72 model
Coil resistance value of 0.092 ohm
(20°C [68°F]) : P96 - P144 models
[TJMU-A]