Mitsubishi P120 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 136 -
HWE09120 GB
Operation
Outdoor unit model
PUHY-P192TSJMU-A
PUHY-P72TJMU-A PUHY-P120TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C /19.4°C [80 °F/67 °F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
4
No. of units in opera-
tion 4
Model - 48/48/48/48
Piping
Main pipe
m [ft]
5[16-3/8]
Branch pipe 10 [32-3/4]
Total pipe length 45 [147-5/8]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 22 [49]
Outdoor
unit
Electric current A 43.5
Voltage V 230
Compressor frequency Hz 52 74
LEV open-
ing
Indoor unit
Pulse
387/387/387/387
SC (LEV1) 100 100
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.76/0.93 [400/135] 2.76/0.93 [400/135]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
69 [156] 73 [163]
Heat exchanger out-
let (TH3) 44 [111] 40 [104]
Accumulator inlet 10 [50] 10 [50]
Accumulator outlet 10 [50] 10 [50]
SCC outlet (TH6) 24 [75] 20 [68]
Compressor inlet 17 [63] 15 [59]
Compressor shell
bottom 47 [117] 42 [108]
Indoor
unit
LEV inlet 21 [70] 21 [70]
Heat exchanger
outlet 10 [50] 10 [50]