Mitsubishi P120 Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 169 -
HWE09120 GB
1. Error Code
Water leakage
2. Cause, check method and remedy
Check that water does not leak from the pipes in such as the humidifier.
1. Error Code
Water supply cutoff
2. Cause, check method and remedy
2600
2601
Cause Check method and remedy
(1) The water tank of the humidifier is empty. Check the amount of supply water.
Check for the solenoid valve and for the connection.
(2) The solenoid valve for humidification is OFF. Check the connector.
(3) Disconnected float switch Check the connecting part.
(4) Poor operation of float switch Check for the float switch.
(5) Frozen water tank Turn off the power source of the water tank to defrost, and
turn it on again.