Mitsubishi P120 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 135 -
HWE09120 GB
2. 2-unit combination
(1) Cooling operation
Operation
Outdoor unit model
PUHY-P168TSJMU-A
PUHY-P72TJMU-A PUHY-P96TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C /19.4°C [80 °F/67 °F]
Outdoor
35°C / - [95 °F/ - ]
Indoor
unit
No. of connected
units
Unit
4
No. of units in opera-
tion 4
Model - 36/36/48/48
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe 10 [32-3/4 ]
Total pipe length 45 [147-5/8]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 17 [37]
Outdoor
unit
Electric current A 37.9
Voltage V 230
Compressor frequency Hz 52 65
LEV open-
ing
Indoor unit
Pulse
325/325/387/387
SC (LEV1) 190 190
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.71/0.90 [393/131] 2.71/0.90 [393/131]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
69 [156] 74 [165]
Heat exchanger out-
let (TH3) 44 [111] 46 [115]
Accumulator inlet 10 [50] 10 [50]
Accumulator outlet 10 [50] 10 [50]
SCC outlet (TH6) 24 [75] 26 [79]
Compressor inlet 17 [63] 14 [57]
Compressor shell
bottom 47 [117] 38 [100]
Indoor
unit
LEV inlet 24 [75] 24 [75]
Heat exchanger
outlet 10 [50] 10 [50]