Mitsubishi Electronics PCFY-NKMU-E Air Conditioner User Manual


 
19
12. Speci cations
PKFY Series
Model
PKFY-P06NBMU-E PKFY-P08NBMU-E PKFY-P12NHMU-E PKFY-P15NHMU-E PKFY-P18NHMU-E
Power source Single 208/230V 60Hz
Capacity
Cooling <BTU/h> 6,000 8,000 12,000 15,000 18,000
Heating <BTU/h> 6,700 9,000 13,500 17,000 20,000
Dimension
H <inch> 11-5/8
W <inch> 32-1/8 35-3/8
D <inch> 8-7/8 9-13/16
Net weight <Ibs> 22 29
Fan Air ow rate
(Low-Middle2-Middle1-High)
DRY <CFM> 170-180-200-210 320-355-390 320-370-405 320-370-425
WET <CFM> 160-170-180-190 290-320-350 290-335-365 290-335-380
Noise level
(Low-Middle2-Middle1-High)
<dB(A)> 32-33-35-36 34-38-42 34-38-42 36-41-45
PCFY Series
Model
PCFY-P15NKMU-E PCFY-P24NKMU-E PCFY-P30NKMU-E PCFY-P36NKMU-E
Power source Single 208/230V 60Hz
Capacity
Cooling <BTU/h> 15,000 24,000 30,000 36,000
Heating <BTU/h> 17,000 27,000 34,000 40,000
Dimension
H <inch> 9-1/16
W <inch> 37-13/16 50-3/8 63
D <inch> 26-3/4
Net weight <Ibs> 53 71 79 84
Fan Air ow rate
(Low-Middle2-Middle1-High)
DRY <CFM>
350-390-420-460 490-530-570-640 710-780-880-990
740-850-950-1090
WET <CFM>
330-370-400-440 470-500-540-610 670-740-840-940
700-810-900-1040
Noise level
(Low-Middle2-Middle1-High)
<dB(A)> 29-32-34-36 31-33-35-37 34-37-40-43 36-39-42-44
PMFY Series
Model
PMFY-P06NBMU-E PMFY-P08NBMU-E PMFY-P12NBMU-E PMFY-P15NBMU-E
Power source Single 208/230V 60Hz
Capacity
Cooling <BTU/h> 6,000 8,000 12,000 15,000
Heating <BTU/h> 6,700 9,000 13,500 17,000
Dimension (Grille)
H <inch> 9-1/16 (1-3/16)
W <inch> 33-5/8 (39-3/8)
D <inch> 1/-9/16 (18-1/2)
Net weight (Grille) <Ibs> 31 (7)
Fan Air ow rate
(Low-Middle2-Middle1-High)
DRY <CFM>
230-250-280-300
250-280-300-320
270-300-340-370
WET <CFM>
200-220-250-270
220-250-270-290
240-270-310-340
Noise level
(Low-Middle2-Middle1-High)
<dB(A)> 27-30-33-35 32-34-36-37 33-35-37-39
1. Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Coolong : Indoor 27°C DB, 81°F DB/19°C WB, 66°F WB, Outdoor 35°C DB, 95°F DB
Heating : Indoor 20°C DB, 68°F DB, Outdoor 7°C DB, 45°F DB/ 6°C WB, 43°F WB
Range of application
The range of working temperatures for both the indoor and outdoor units of the series Y is as below.
Caution:
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
Mode Indoor unit
Outdoor unit
PUHY
Cooling
15°C - 24°C WB, 59˚F - 75˚F WB –5°C - 43°C DB, 23˚F - 110˚F DB
Heating
15°C - 27°C DB, 59˚F - 81˚F DB
–15°C - 15.5°C WB, 5˚F - 60˚F WB
Note: As an applicable humidity standard for both indoors and outdoors, we recommend use within a range of 30 - 80% relative humidity.
Warning:
If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since there may be a refrigerant
leak. Be sure to ask the service representative whether there is refrigerant leakage or not when repairs are carried out.
The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak, however, if refrigerant gas leaks indoors, and comes
into contact with the re of a fan heater, space heater, stove, etc., harmful substances will be generated.