Lochinvar 400 Boiler User Manual


 
3 Troubleshooting
34
Table 3-1 Troubleshooting Chart - No Display
Service Manual
FAULT CAUSE CORRECTIVE ACTION
No Display
- No 120 vac supplied to unit.
• Check external line switch, fuse, or breaker.
• Check position of ON/OFF switch. Turn switch to the
ON position.
• Check 120 vac through the ON/OFF switch.
• Check wiring harness connection between display
board and main control board. Connect
harness at both points.
- No voltage through the switch. • Replace switch.
- Bad display board. • Replace board.
- Bad main control board. • Replace the main control board.
- Blown fuse.
• Replace fuse F3 on the main control board, see
page 33 of this manual.
No Burner
Operation
- Main control board temperature set point
satisfied.
• Review temperature setting.
- Remote thermostat satisfied. • Review remote thermostat setting.
- Outside air temperature above Warm
Weather Shutdown (WWSD) set point for
main control board.
• Check location of outside air sensor. Check
resistance of outdoor air sensor and compare to Table
3-2B on page 35 of this manual.
- Unit locked out on fault.
• Consult display for specific fault. Refer to fault
descriptions on page 37 of this manual for corrective
actions.
- Unit in Shutdown Mode. • Take unit out of Shutdown Mode.
Unit Does
Not Modulate
Above 50%
- Ramp delay active.
• Check ramp delay parameter settings. Optional PC
software required.
• Turn ramp delay feature off. See page 23 of this
manual for instructions on how to turn this feature off.
- Boiler controlled by BMS.
• Check BMS parameter settings. Optional PC
software required.
- Flue sensor open.
• Verify that the flue sensor is located in the flue outlet.
• Check wiring connections at the flue sensor.
• Check the resistance of the flue sensor and compare
to Table 3-2D on page 35 of this manual.