Lennox International Inc. 506586-01 Heat Pump User Manual


 
Page 43
XP17 SERIES
Table 15. Compressor Fault and Lockout LED Codes and Related icomfort Touch
®
Thermostat Alert Codes
NOTE Ċ See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
Heat Pump Control
LEDs
icomfort
Touch
®
Thermostat
Display
Condition
Possible
Cause(s)
Solution
Clearing Status
DS15
Yellow
DS13
Red
Off On
Moderate/
Critical
3
Alert
Code 400
Compressor
internal
overload trip
Thermostat
demand signal Y1
is present, but
compressor not
running
1
Compressor protector is open.
S Check for high head pressure
S Check compressor supply voltage
2
Outdoor unit power disconnect is open.
3
Compressor circuit breaker or fuse(s) is open.
4
Broken wire or connector is not making contact.
5
Low or high pressure switch open if present in the
system.
6
Compressor contactor has failed to close.
Clears the error
after current is
sensed in the
run and start
winding for two
seconds, ser-
vice removed or
power reset.
1 flash
then pause
Off
Critical Alert
Code 401
Long run time.
Compressor is
running extremely
long run cycles.
1
Low refrigerant charge.
2
Evaporator blower is not running.
S Check blower relay coil and contacts
S Check blower motor capacitor
S Check blower motor for failure or blockage
S Check evaporator blower wiring and connec-
tors
S Check indoor blower control
S Check thermostat wiring for open circuit
3
Evaporator coil is frozen.
S Check for low suction pressure
S Check for excessively low thermostat setting
S Check evaporator airflow (coil blockages or re-
turn air filter)
S Check ductwork or registers for blockage.
4
Faulty metering device.
S Check TXV bulb installation (size, location and
contact)
S Check if TXV/fixed orifice is stuck closed or de-
fective
5
Condenser coil is dirty
.
6
Liquid line restriction (filter drier blocked if present)
.
7
Thermostat is malfunctioning
.
S Check thermostat sub−base or wiring for short
circuit
S Check thermostat installation (location and lev-
el)
Clears the error
after 30 consec-
utive normal run
cycles, or after
power reset.
2 flashes
then pause
Off
Critical Alert
Code 402
System
pressure trip
Indicates the
compressor
protector is open
or missing supply
power to the
compressor.
1
High head pressure.
S Check high pressure switch if present in sys-
tem
S Check if system is overcharged with refrigerant
S Check for non−condensable in system
2
Condenser coil poor air circulation (dirty, blocked,
damaged).
3
Condenser fan is not running.
S Check fan capacitor
S Check fan wiring and connectors
S Check fan motor for failure or blockage
4
Return air duct has substantial leakage.
Clears after four
consecutive
normal com-
pressor run
cycles, or after
power reset.
3 flashes
then pause
Off
Moderate
Alert Code
403
Short cycling
Compressor is
running less than
three minutes.
1
Thermostat demand signal is intermittent.
2
Time delay relay or heat pump control is defective.
3
If high pressure switch is present, see flash code 2
information.
Clears after four
consecutive
normal com-
pressor run
cycles, or after
power reset.