Lennox International Inc. 506510-01 Air Conditioner User Manual


 
Page 38
506510−01
Outdoor Main
Control LEDs
Clearing Status
Solution
Possible
Cause(s)
Condition
DS15
Yellow
Clearing Status
Solution
Possible
Cause(s)
Condition
DS13
Red
5 Flashes
then
Pause
OFF Open Circuit
Compressor has
an open circuit
due to power dis-
connection, fuse
is open or other
similar conditions.
1
Outdoor unit power disconnect is open.
2
Unit circuit breaker or fuse(s) is open.
3
Unit contactor has failed to close.
S Check compressor contactor wiring and con-
nectors
S Check for compressor contactor failure (burned,
pitted or open)
S Check wiring and connectors between supply and
compressor
S Check for low pilot voltage at compressor con-
tactor coil
4
High pressure switch is open and requires manual
reset.
5
Open circuit in compressor supply wiring or con-
nections.
6
Unusually long compressor protector reset time due
to extreme ambient temperature.
7
Compressor windings are damaged.
S Check compressor motor winding resistance
Clears after one normal
compressor run cycle or
power reset.
6 Flashes
then
Pause
OFF
Open Start
Circuit
Current not
sensed by Start
transformer.
1
Run capacitor has failed.
2
Open circuit in compressor start wiring or connec-
tions.
S Check wiring and connectors between supply and
the compressor S terminal
3
Compressor start winding is damaged.
S Check compressor motor winding resistance
Clears when amperage is
detected in RUN and
START sensors, or after
power reset.
7 Flashes
then
Pause
OFF
Open Run
Circuit
Current not
sensed by run
transformer.
1
Open circuit in compressor start wiring or connections.
S Check wiring and connectors between supply and
the compressor R terminal
2
Compressor start winding is damaged.
S Check compressor motor winding resistance
Clears when amperage is
detected in RUN and
START sensors, or after
power reset.
8 Flashes
then
Pause
OFF
Welded
Contactor
Compressor
always runs
1
Compressor contactor failed to open.
2
Thermostat demand signal not connected to module.
Clears after one normal
compressor run cycle or
after power reset.
9 Flashes
then
Pause
OFF
Secondary
Low Voltage
24VAC is below
18VAC.
1
Control circuit transformer is overloaded.
2
Low line voltage (contact utility if voltage at disconnect
is low).
S Check wiring connections
Clears after voltage is higher
than 20VAC for two
seconds, or after power
reset.
Fast simultaneous
flashing of DS11,
DS13, DS14 and
DS15
OEM Mode Factory Test Mode.