Lennox Hearth SHRL 33/40 DV INS Indoor Fireplace User Manual


 
7
NOTE: DIAGRAMS AND ILLUSTRATIONS ARE NOT TO SCALE
NEW YORK CITY, NEW YORK (MEA)
(NYC MEA Approval #138-07-E)
Installation of these appliances are approved for installation in New York
City in the US state of New York.
COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS
(Massachusetts Approval #G3-0508-369)
These appliances are approved for installation in the US state of Mas-
sachusetts if the following additional requirements are met:
Install this appliance in accordance with Massachusetts Rules and
Regulations 248 C.M.R.
Installation and repair must be done by a plumber or gas fitter licensed
in the Commonwealth of Massachusetts.
The flexible gas line connector used shall not exceed 36 inches (92
centimeters) in length.
The individual manual shut-off must be a T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed
less than seven (7) feet above the finished grade must comply with the
following additional requirements:
A hard wired carbon monoxide detector with an alarm and battery
back-up must be installed on the floor level where the gas fireplace
is installed. The carbon monoxide detector must comply with NFPA
720, be ANSI/UL 2034 listed and be ISA certified.
A metal or plastic identification plate must be permanently mounted to
the exterior of the building at a minimum height of eight (8) feet above
grade and be directly in line with the horizontal termination. The sign
must read, in print size no less than one-half (1/2) inch in size, GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.