Lennox Hearth EDVI35 Indoor Fireplace User Manual


 
7
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Top of Insert
(see "C" on Fig. 3)
2
3
4
5
6
7
8
9
10
11
12
0
0
18"
17"
16"
15"
1
\
14"
D
C
Figure 3
Figure 4a
Table 5
MINIMUM CLEARANCES TO COMBUSTIBLES: EDVI25, EDVI30 & EDVI35
These appliances can be installed in most residential
fi replace confi gurations. If installed close to an adjacent
wall, ensure that the minimum clearances to combustible
surfaces are maintained. A local building inspector should
review your plans prior to installation.
Refer to Figures 3, 4a, 4b and 5 for Clearances to Combus-
tibles. Minimum clearances include spacers/standoffs or
surfaces to combustible construction.
Notes for Table 5:
* This includes any projections such as shelves, window
sills, mantels, spacers/standoffs or surfaces to com-
bustible construction etc. above the appliance. Paint or
lacquer used to fi nish the mantel must be heat resis-
tant in order to avoid discoloration.
** If hearth is elevated, subtract 1 inch of hearth
extension required for every 2 inches of height (see
Figure 6).
Mantel
Ceiling (or)
Alcove Height
Side
Wall
Clearances to Combustibles
Inches (millimeters)
Min.
Min.
Min.
Min.
Min.
Min.
Min.
MAX.
MAX.
Min.
Max.
See Fig. 3 & 4a
0" (0 mm) 0" (0 mm)
**16" (406 mm)
**16" (406 mm)
49" (1245 mm) 48" (1219 mm)
50" (1270 mm)
49" (1245 mm)
36" (914 mm) 36" (914 mm)
8" (203 mm)
8" (203 mm)
64" (1626 mm) 64" (1626 mm)
See Fig. 3 & 4a
See Fig. 4a
See Fig. 4a
0" (0 mm)
**16" (406 mm)
44" (1118 mm)
45" (1143 mm)
36" (914 mm)
8" (203 mm)
64" (1626 mm)
See Fig. 3 & 4b
See Fig. 4b
A
Side Wall
B
Ceiling or Alcove Height
C *
Mantel Height
D*
Mantel Projection from Wall
E
Clearance to Floor
F**
Hearth Protection
G
H
Alcove Width
Alcove Depth
(from Fireplace Face)
EDVI30
EDVI35
EDVI25
Hearth Protection Width
I
A
G
E
C
B
Hearth Protection
Side View
Top of Insert
Mantel Clearance, Models: EDVI30 &
EDVI35: The mantel should be located
in the shaded area (light gray) shown
below.
Existing Fireplace Hearth
F
15"
14"
2"
4"
6"
7"
At 7" hearth height, no hearth extension is required
16"
Figure 6
Side View
of Insert
Hearth Protection: For every 2" of hearth height,
subtract 1" of hearth extension required.
Top View Alcove
Hearth
H
Figure 5
Insert
Fireplace
I
Alcove Minimum Width: The specifi ed minimum width of the
alcove cannot be reduced with the use of wall protection.
Clearances
Top of Insert louver
(see "C" on Fig. 3)
0
0
8”
5”
1”12”
15 1/2"
13"
11"
\
8 1/2"
D
C
Figure 4b
Side View
Mantel Clearance, Model: EDVI25: The
mantel should be located in the shaded
area (light gray) shown below.
13 1/2"