Kenmore 153.335862 Water Heater User Manual


 
Installation Instructions (cont'd)
Gas Piping
AWARNING
Make sure the gassuppliedisthe same type listedon the
model rating plate.The inlet gaspressuremust not exceed
10.5in.water column(2.6kPa)for natural gasor 13in,water
column (3.2kPa)for propane(LR) gas.The minimum inlet
gaspressurelistedon the model rating plateisfor the pur-
poseofinputadjustment.
AWARNING
If the gas control valve is subjected to pressuresexceeding ½ [
pound per square inch (3.5kPa), the damage to the gas con-
tro valve could result in a fire or explosion from eak ng gas.
AWARNING
If the main gas line shutoff serving all gas appliances is used, I
also turn "off" the gasat each appliance. Leave all gas appli-
ances shut off until the water heater installation scomp ete.
AWARNING I
Use pipe joint compound or teflon tape marked as being
resistant to the action of petroleum [Propane (L.R)] gases.
SEDIMENT TRAP
A sediment trap shall be installed as close to the inlet of the
water heater as practical at the time of water heater installation.
The sediment trap shall be either a tee fitting with a capped nip-
pie in the bottom outlet or other device recognized as an effec-
tive sediment trap. Ifa tee fitting is used, it shall be installed in
conformance with one of the methods of installation shown
below.
Connecting the gas piping to the gas control valve of the water
heater can be accomplished by either of the two methods shown.
GAS PIPING WITH
FLEXIBLE CONNECTOR
A gas line of sufficient size must be run to the water heater.
Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA 54 and the gas company con-
cerning pipe size.
There must be:
A readily accessible manual shut off valve in the gas supply line
serving the water heater, and
A drip leg (sediment trap) ahead of the gas control valve to help
prevent dirt and foreign materials from entering the gas control
Valve,
A flexible gas connector or a ground joint union between the
shutoffvalve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the
water heater. Use a soapy water solution, not a match or open
flame. Rinse offsoapy solution and wipe dry.
MANUAL SHUT OFF [j_( AS SUPPLY PIPING
VALVE
FLEXIBLE GAS CONNECTOR
LABELED ASCOMPLYING
WITH ANSI STANDARDS
LOOP
GROUND JOIN_
UNION (Optional)
3" MIN.
Standard Models are for installation up to 3,300 feet above sea
level.
High Altitude Models are for installation from 3,300 to 5,500
feet above sea level.
If a standard model is installed above 3,300 feet or a high altitude
model is installed above 5,500 feet, the input rating must be
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact your local Sears Service Center or gas utility for further
information.
AWARNING
I The appliance and its gas connection must be leak tested
[ before placing the appllance in operation.
GAS
CONTROL
VALVE
GAS PIPING WITH ALL BLACK IRON
PIPE TO GAS CONTROL
MANUAL SHUT OFF _CAS SUPPLYPIPING
VALVE
GROUND
UNION
BLACK PIPE
(Sediment
trap)
CAP
GAS
CONTROL
VALVE
AWARNING
The appliance and its individual shutoff valve must be discon-
nected from the gassupplypiping system during any pressure
testing of the gas system at test pressures in excess of I/2
pound per square inch(3.5kPa).
The appliance must beisolatedfrom the gassupplypipingsys-
tem by closingits individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pres-
suresequal or lessthan I/2 pound per squareinch(3.5kPa).
19
=t WARNING
Contaminants in the gas lines may cause improper operation
of the gas control valve that may result in fire or explosion.
Before attaching the gas line be sure that all gaspipe isclean
on the inside. To trap any dirt or foreign material in the gas
supply line, a drip leg (sometimes called a sediment trap)
must be incorporated in the piping. The drip leg must be
readily accessible. Install in accordance with the "Gas Piping"
section. Refer to the latest edition of the National Fuel Gas
Code, ANSI Z223. I, also referred to asNFPA 54.