Johnson Controls CSV060B-240B Air Conditioner User Manual


 
FORM 145.15-IOM7 (412)
18 JOHNSON CONTROLS
CSV180B
CSV240B
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4800 634 1.20 697 1.42 757 1.62 813 1.84 867 2.06 918 2.30 968 2.52 1015 2.76 1065 3.02 1109 3.32
5400 701 1.66 758 1.90 812 2.14 864 2.38 914 2.62 962 2.88 1009 3.12 1053 3.38 1097 3.66 1139 3.92
6000 765 2.22 817 2.48 867 2.74 916 3.00 962 3.28 1007 3.54 1051 3.82 1093 4.10 1134 4.38 1174 4.68
6600 832 2.90 880 3.20 927 3.48 972 3.76 1015 4.06 1057 4.34 1099 4.64 1139 4.96 ~ ~ ~ ~
7200 900 3.72 945 4.02 988 4.34 1030 4.64 1070 4.96 ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Standard Factory Drive + 3 HP
Optional Hi-Static Drive + 5 HP
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
2.0
1.8
1.4
1.6
Field Supplied Low Static
Drive
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6400 705 1.96 760 2.22 812 2.48 862 2.72 910 3.02 956 3.28 1001 3.56 1043 3.84 1085 4.12 1125 4.42
7200 788 2.76 837 3.06 884 3.34 930 3.64 952 3.78 995 4.08 1037 4.38 1078 4.70 1118 5.00 1156 5.32
8000 861 3.70 906 4.02 950 4.34 992 4.66 1033 4.98 1073 5.32 1111 5.66 1149 5.98 1186 6.32 1222 6.68
8800 949 4.94 970 5.12 1010 5.46 1049 5.82 1087 6.18 1125 6.52 1161 6.90 1197 7.26 ~ ~ ~ ~
9600 1028 6.34 1066 6.72 1103 7.10 1139 7.48 ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Optional Hi-Static Drive +7.5HP
Standard Factory Drive + 5 HP
Field Supplied Low Static Drive
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
2.0
1.8
1.4
1.6