Johnson Controls CSV060B-240B Air Conditioner User Manual


 
FORM 145.15-IOM7 (412)
JOHNSON CONTROLS 17
FAN PERFORMANCE
CSV060B
CSV096B
CSV120B
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1600 645 0.29 733 0.36 814 0.43 888 0.50 958 0.57 1024 0.64 1087 0.72 1154 0.83 1211 0.91 1245 0.99
1800 708 0.40 788 0.48 863 0.55 933 0.63 999 0.71 1061 0.79 1121 0.87 1178 0.95 1233 1.04 1295 1.17
2000 763 0.52 837 0.61 907 0.69 973 0.77 1035 0.86 1095 0.95 1152 1.04 1207 1.13 1260 1.22 1311 1.31
2200 836 0.69 904 0.78 969 0.87 1030 0.97 1089 1.06 1145 1.15 1199 1.25 1252 1.35 1303 1.45 ~ ~
2400 898 0.88 961 0.98 1021 1.08 1079 1.18 1135 1.28 1188 1.38 1240 1.48 ~ ~ ~ ~ ~ ~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
0.2
0.4
0.6
0.8
1.0
1.2
Optional Hi-Static Drive + 1.5 HP
Standard Drive + 1 HP
Field Supplied Low Static
Drive
1.4
1.6
1.8
2.0
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2400 510 0.31 600 0.45 672 0.60 741 0.78 810 0.96 878 1.14 936 1.33 982 1.54 1033 1.76 1074 2.00
2800 538 0.44 628 0.57 700 0.71 778 0.89 830 1.10 890 1.29 950 1.50 1010 1.72 1048 1.92 ~ ~
3200 599 0.62 675 0.79 745 0.98 815 1.18 875 1.38 927 1.58 985 1.78 1037 1.99 ~ ~ ~ ~
3600 661 0.86 730 1.03 795 1.23 853 1.43 915 1.64 973 1.85 ~ ~ ~ ~ ~ ~ ~ ~
4000 712 1.10 773 1.28 830 1.50 888 1.72 946 1.95 ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
Standard Drive + 1.5 HP
Field Supplied Low Static
Drive
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Optional Hi-Static Drive + 2 HP
1.4
1.6
1.8
2.0
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
SUPPLY AIR BLOWER PERFORMANCE
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3200 599 0.62 675 0.79 745 0.98 815 1.18 875 1.38 927 1.58 984 1.78 1037 1.99 1082 2.22 1128 2.42
3600 661 0.86 730 1.03 795 1.23 853 1.43 915 1.64 973 1.85 1020 2.10 1070 2.37 1114 2.67 1160 2.89
4000 712 1.10 773 1.28 830 1.50 888 1.72 946 1.95 1004 2.19 1062 2.44 1098 2.70 1146 2.97 ~ ~
4400 768 1.42 824 1.62 877 1.82 930 2.04 985 2.30 1035 2.60 1085 2.90 ~ ~ ~ ~ ~ ~
4800 822 1.78 875 1.98 925 2.20 975 2.43 1026 2.68 1078 2.96 ~ ~ ~ ~ ~ ~ ~ ~
1. Blower performance includes evaporator coil and 2" filters
2. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Decrease airflow downward as necessary.
Field Supplied Low Static
Drive
SUPPLY
CFM
0.2
0.4
0.6
0.8
1.0
1.2
AVAILABLE EXTERNAL STATIC PRESSURE - Inches W.C. ¹
Optional Hi-Static Drive + 3 HP
Standard Drive + 2 HP
1.4
1.6
1.8
2.0