OTHERS ARE CALCULATED VALUES BASED ON THE BATTERY MANUFACTURER'S DATA FOR BACK UP
TIME.
APPENDIX B – Optional Main Input & Main Output Breakers
for various models (*All Values are typical as reference only)
TABLE B-1: External Output Breaker (Standard KAIC)
Output Voltages
KVA
120 Vac 240 /120 VAC
3
40 Amps, 120 VAC,
1 Pole, 14 KAIC
OLP P/N: 2025-783
20 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-788
5
70 Amps, 120 VAC,
1 Pole, 14 KAIC
OLP P/N: 2025-997
40 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-791
7.5
100 Amps, 120 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-999
50 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-792
10
125 Amps, 120 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-759
70 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-794
12.5
1750 Amps, 120 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-468
80 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-795
15
200 Amps, 120 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-541
100 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-797
TABLE B-2: Output Breaker (High KAIC)
Output Voltages
KVA
120 Vac 240 Vac
3
40 Amps, 120 VAC,
1 Pole, 42 KAIC
OLP P/N: 2025-799
20 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-762
5
70 Amps, 120 VAC,
1 Pole, 42 KAIC
OLP P/N: 2025-998
40 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-766
7.5
100 Amps, 120 VAC,
2 Pole, 42 KAIC
OLP P/N: 2025-803
50 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-767
10
125 Amps, 120 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-759
70 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-769
12.5
1750 Amps, 120 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-468
80 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-770
15
200 Amps, 120 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-541
100 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-894