IBM UPS1481 UNIT Smoke Alarm User Manual


 
OnLine Power
(6002-1646) REV.X8 12
TABLE 2-1
SITE PLANNING SPECIFICATIONS FOR KVA UNIT
MODEL
NUMBER
IkW / kVA
INPUT
VOLTAGE
INPUT
AMP
OUTPUT
VOLTAGE
OUTPUT
AMP
DC
VOLT
DC
AMP
QTY. BATT
PER SET
APPROX.
W/O BATT
WEIGHT
1
WR3.0A58FPT1 3.0 120 40 120/240 25.00 @120 96V 43A 8
2
WR3.0B58FPT1 3.0 208 19 120/240 96V 43A 8
3
WR3.0D58FPT1 3.0 240 19 120/240 12.50 @240 96V 43A 8
5
WR5.0A58FPT1 5.0 120 58 120/240 41.70 @120 120V 57A 10
6
WR5.0B58FPT1 5.0 208 30 120/240 120V 57A 10
7
WR5.0D58FPT1 5.0 240 30 120/240 21.00 @240 120V 57A 10
9
WR7.5B58FPT1 7.5 208 44 120/240 62.5 @ 120 120V 86A 10
10
WR7.5D58FPT1 7.5 240 41 120/240 31.3 @240 120V 86A 10
12
WR010B58FPT1 70.0 208 44 120/240 83.0 @ 120 192V 71A 16
13
WR010D58FPT1 10.0 240 58 120/240 41.5 @240 192V 71A 16
15
WR012B58FPT1 12.5 208 73 120/240 104.2 @ 120 192V 88A 16
16
WR012D58FPT1 12.5 240 69 120/240 52.1 @240 192V 88A 16
18
WR015B58 FPT1 15.0 208 85 120/240 125.0 @ 120 240V 84A 20
19
WR015D58FPT1 15.0 240 83 120/240 62.5 @240 240V 84A 20
21
WR3.0A01FPN1 3.0 120 40 120 25.00 @ 120 96V 43A 8
22
23
25
WR5.0A01FPN1 5.0 120 58 120 41.70 @ 120 120V 57A 10
26
27
29
30
32
33
35
36
38
39
NOTE: FP DENOTES – FIRE PROTECTION Fire Alarm Back-up UPS1481 SERIES.