BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
63-4524—01 24
Table 10. Property enumeration sets for MV objects. (Continued)
6. Enumeration sets for MV26 depends on Control Type (BV75) value and Pipe Number (MV52) value upon device dis-
covery. If required enumeration is not present, set BV75 and MV52 to desired value and rediscover MV26 object.
Available enumeration will now reflect required configuration.
7. Available object name, state text and default value depends on Control Type (BV75) value and Pipe Number (MV52)
upon device discovery.
8. Enumeration sets for MV27 depends on Control Type (BV75) value and Pipe Number (MV52) value upon device dis-
covery. If required enumeration is not present, set BV75 and MV52 to desired value and rediscover MV27 object.
Available enumeration will now reflect required configuration.
9. Available object name, state text and default value depends on Control Type (BV75) value and Pipe Number (MV52)
upon device discovery.
MV17 Index Function MV58 State Text Index Default Value
1 1 Low - 2 Med - 3 High High
2 1 Low - 2 High High
3 1 Low - 2 Med - 3 High - 4 Auto High
4 1 Low - 2 High - 3 Auto High
5 1 Auto -2 On Auto
Object Name Object ID BACnet Index Text Default value
Heating Valve Status
Note 6
MV 26 Note 7 Note 7 Note 7
Cooling Valve Status
Note 8
MV 27 Note 9 Note 9 Note 9
Fan Status MV 28
1Off
Off
2Low
3Med
4High
Effective Occupancy MV 33
1 Occupied
Depends on local
occupancy
2 Unoccupied
3 Temporary Occupied
4 Stand-by
BV75 Value MV52 Index MV26 Object
Name
Function MV26 State Text Index Default Value
On/Off 1 (2 pipe) Unused Output N/A N/A
2 (4 pipe) Heating Valve
Status
1 Closed – 2 Open Closed
Floating 1 (2 pipe) Unused Output N/A N/A
2 (4 pipe) Heating Valve
Status
1 Stopped - 2 Opening - 3 Closing Stopped