BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
63-4524—01 10
TB7200 Integration – Graphical User Interface (GUI) objects
The following objects should be typically used in a GUI:
Room Temperature (AV7);
Occupied and Unoccupied Heat Setpoints (AV 39 and AV43);
Occupied and Unoccupied Cool Setpoints (AV 40 and AV34);
Outdoor Temperature (AV 9);
Supply Temperature (AI12) (If available);
Occupancy Command (MV18);
System Mode (MV16);
Heating Valve Status (MV26);
Cooling Valve Status (MV28);
PI Heating Demand (AV21)
PI Cooling Demand (AV22)
Window Alarm (BI 35);
Filter Alarm (BI 36);
Service Alarm (BI 37)
Fig. 7. Example of graphical user interface objects.