BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
63-4524—01 20
Standard Object Types Supported
Table 6. Standard object types supported.
a
Present_Value and Out_of_Service properties are writable for every AV objects except :
PI Heating Demand (AV21)
PI Cooling Demand (AV22)
b
Present_Value property for Room Temperature (AV7) and Room Humidity (AV10) is writable only if Room Temp
Override (BV8) is enabled and Room Humidity Override (BV11) is enabled respectively.
c
Object_Name property is writable for the following object only :
Room Temperature (AV7)
d
Present_Value and Out_of_Service properties are writable for every MV objects except :
Heating Valve Status (MV26)
Cooling Valve Status (MV27)
Fan Status (MV28)
Effective Occupancy (MV33)
List of Proprietary Properties
Table 7. Proprietary Properties.
Object Type
Supported
Objects
Dynamically
Creatable
Dynamically
Deletable
Optional
Properties
Supported
Writable Properties
Analog Input
 
Reliability Out_of_Service
Analog Value
 
Reliability
Present_Value
a,b
Out_of_Service
a
Object_Name
c
Binary Input
 
Reliability
Active_Text
Inactive_Text
Out_of_Service
Binary Value
 
Reliability
Active_Text
Inactive_Text
Present_Value
Out_of_Service
Device
 
Max_Master
Max_Info_frames
Object_Identifier
Object_name
Max_Master
Group
 
N/A N/A
Multi-state Value
 
Reliability
States_Text
Present_Value
d
Out_of_Service
d
Property name ID BACnet Data type Description
Major_Version 1000 CharacterString
The version number of the BACnet communications
module. This is the hardware version number
MS/TP_Address 1001 Unsigned Display the MAC layer address of the module
MS/TP_Baud_Rate 1002 Unsigned Display the communication baud rate of the module
Sensor_Offset 1005 REAL
Display the temperature or humidity calibration value.
The range is –5.0 deg F to 5.0 deg F for a temperature
and –15% to 15% for humidity.