Enumeration Sets for MV Objects
Table 10. Property enumeration sets for MV objects.
NOTES:
1. Enumeration sets for MV16 depends on Sequence of Operation (MV15) value upon device discovery. If required
enumeration is not present, set MV15 to desired value and rediscover MV16 object. Available enumeration will now
reflect required configuration.
2. Default value of MV16 depends on MV15 value upon device discovery.
3. Enumeration sets for MV17 depends on Fan Mode Sequence (MV58) value upon device discovery. If required enu-
meration is not present, set MV58 to desired value and rediscover MV17 object. Available enumeration will now
reflect required configuration.
4. Available state text and default value depends on Fan Mode Sequence (MV58) value upon device discovery.
5. Same as Note 4.
Object Name Object ID BACnet Index Text Default value
Sequence of
Operation
MV 15
1 Cooling Only
Heating Only
2 Heating Only
3 Cooling & Reheat
4 Heating & Reheat
5 Cool/Heat4P
6 Cool/Heat4P&Reht
System Mode
Note 1
MV 16
1Off
Note 2
2Auto
3Cool
4Heat
Fan Mode
Note 3
MV 17 1, 2, 3 or 4 Note 4 Note 5
Occupancy
Command
MV 18
1 Local Occupancy
Depends on network
command
2 Occupied
3 Unoccupied
Keypad Lockout MV 19
1 Level 0
Level 0
2 Level 1
3 Level 2
4 Level 3
5 Level 4
6 Level 5
MV15 Index Function Default Value is BV50
Enabled
Default Value is BV50
Disabled
1 Cooling Only Cool Cool
2 Cooling with Reheat Auto Heat
3 Heating Only Heat Heat
4 Heating with Reheat Heat Heat
5 Cooling/Heating 4 Pipes Auto Heat
6 Cooling/Heating 4 Pipes with Reheat Auto Heat