Honeywell T7100D Thermostat User Manual


 
T7100D,E,F MICROELECTRONIC COMMERCIAL THERMOSTATS AND Q7100A,C,D SUBBASES
68-0163—3 6
Mounting Thermostat on Subbase
Mount the thermostat on the subbase after the subbase is
installed.
1. Engage the tabs at the top of the thermostat and
subbase. See Fig. 10.
2. Press the lower edge of the case to close and latch.
NOTE: To remove the thermostat from the wall, first pull out
at the bottom of the thermostat then remove the top.
Fig. 10. Mounting thermostat on subbase.
Using Thermostat Keys
The thermostat keys are used to:
set temperature,
display present setting,
configure Installer Setup,
check Self-Test.
Select models have keys to:
temporarily override the temperature,
set the system operation,
set the fan operation.
See Fig. 11 for the location of the keys.
M6799A
B.
PRESS LOWER EDGE
OF CASE TO LATCH.
ENGAGE
TABS AT TOP OF
THERMOSTAT AND SUBBASE.
A.
Fig. 11. Thermostat key locations, descriptions.
SETTINGS
System and Fan Settings
System settings control the thermostat operation as follows:
Em. Heat (Q7100C only): Emergency heat relay is
automatically controlled by the thermostat. The cooling
system is off. The compressor is de-energized.
Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between
heating and cooling operation, depending on the indoor
temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously.
Auto: Equipment controls fan.
The system default setting is Heat and the fan default setting
is Auto. Use the keys to change to the desired settings.
See Fig. 11.
NOTE: Always press the keys with your fingertip or similar
blunt tool. Sharp instruments like a pen or pencil
point can damage the keyboard.
Temperature Settings
The default setpoint for heat is 70°F (21°C) and for cool is
78°F (25.5°C). Press the increase or decrease key to
change the present setting. To change between heat and
cool, press the Information i key until the setting to be
changed appears. Press the increase or decrease key to
adjust the setting.
Override Temperature Settings
(Select Models)
The T7100 temperature settings can be overridden in three
ways:
Using the Override key (T7100F only), acting as a toggle.
Using a remote setback timer.
Using an occupancy sensor.
The temperature settings change based on the Installer
Setup 27.
NOTE: The Installer Setup 27 is factory set at zero degrees
so this setting must be changed for the temperature
to change.
The Override key temporarily changes the current
temperature to a preset offset. The remote timer and
occupancy sensor opens (temporary setpoint) or closes
(comfort setpoint) contacts according to the setting.
See Table 5.
Table 5. Examples of Temperature Overrides.
System
Setting
Comfort
Setpoint
Installer Setup
Number 27 Setting
Temporary
Setpoint
Heat 68°F 10°F 58°F
Cool 74°F 10°F 84°F
M6800C
DISPLAY PRESENT SETTINGS AND
SCROLLS THROUGH INSTALLER
SETUP (INFORMATION KEY)
CHANGE TEMPERATURE
SETTING TEMPORARILY
(SELECT MODELS)
i
SELECT SYSTEM
OPERATION
SELECT
FAN OPERATION
INCREASE TEMPERATURE
SETTING
DECREASE TEMPERATURE
SETTING