Honeywell T7100D Thermostat User Manual


 
T7100D,E,F MICROELECTRONIC COMMERCIAL THERMOSTATS AND Q7100A,C,D SUBBASES
68-0163—3
15
Fig. 22. Typical hookup of Q7100C1073 in three-stage heat, one-stage cool heat pump system.
Includes remote temperature sensor, remote setback timer.
TROUBLESHOOTING GUIDE
EQUIPMENT
MONITOR 2
L1
(HOT)
L2
M15325A
FAN
RELAY
D
OE W3 Y2
COOL
CHANGEOVER
VALVE
HEAT
CHANGEOVER
VALVE
SUBBASE
2
XB G
EM. HT.
RELAY
R
TD
REMOTE
TEMPERATURE
SENSOR
AUX. HT.
RELAY
Y1
T
COMPRESSOR
CONTACTOR 2
CAUTION: EQUIPMENT DAMAGE. CAN BURN OUT THERMOSTAT. DO NOT CONNECT POWER TO THE D TERMINAL.
DO NOT PARALLEL SEVERAL THERMOSTATS FROM A SINGLE SOURCE UNLESS ISOLATION RELAYS ARE USED.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
SELECT MODELS HAVE LEDS.
X4 NEEDS TO BE JUMPERED TO TERMINAL X.
1
2
REMOTE
SETBACK
TIMER
1
3
COMPRESSOR
CONTACTOR 1
X3
EQUIPMENT
MONITOR 1
X1X4
4
3
4
(continued)
Symptom Possible Cause Action
Display does not
come on.
Thermostat is not being
powered.
Check that X terminal is connected to the system transformer.
Check for 24 Vac between X and R or RH terminals.
If missing 24 Vac:
Check if the circuit breaker is tripped; if so, reset the circuit
breaker.
Check if the system fuse is blown; if so, replace the fuse.
Check if the power switch on the HVAC equipment is in the
Off position; if so, set to the On position.
Check wiring between thermostat and HVAC equipment and
replace any broken wires and tighten any loose connections.
If 24 Vac is present, proceed with troubleshooting.
Temperature
display is incorrect.
Room temperature display has
been reconfigured.
Enter Installer Setup 37 and reconfigure the display.
Thermostat is configured for °F
or °C display.
Enter Installer Setup 14 and reconfigure the display.
Bad thermostat location. Relocate the thermostat.
Display shows two dashes and
a degree sign.
Installer Setup 22 is set for remote sensing and the sensor is missing or
the circuit is open or shorted.
Temperature
settings will not
change. (Example:
Cannot set the
heating higher or
the cooling lower.)
The upper or lower temperature
limits were reached.
Check the temperature setpoints:
Heating limits are 40 to 90°F (7 to 31°C).
Cooling limits are 45 to 99°F (9 to 37°C).
Heating does not
come on.
No power to the thermostat. Check that X terminal is connected to the system transformer.
Check for 24 Vac between X and R or RH terminals.
If missing 24 Vac:
Check if the circuit breaker is tripped; if so, reset the circuit
breaker.
Check if the system fuse is blown; if so, replace the fuse.
Check if the system switch at the equipment is in the Off
position; if so, set to On position.
Check wiring between thermostat and HVAC equipment and
replace any broken wires and tighten any loose connections.
If 24 Vac is present, proceed with troubleshooting.